Using the master actuator and its extension modules, several types of channels are available.
When configuring the extensions used on the system, the following types of actuators are available:
Switching channels can be configured has:
Switching channels can be configured has:
Dimming channels can be configured has:
Analog channels can be configured has:
LED channels can be configured has:
For each logic channel, the following logic function can be configured:
| CHANNEL TYPE | EXTENSION TYPE | COMPATIBLE MODULES |
|---|---|---|
| Switch ON/OFF Staircase lighting/pulses Flash Shutter Control Blind Control | Master Switching Actuators | MSA-810 SAE-810 / SAE-2410 SAE-816 DOE-825 |
| ON/OFF Valve control PWM Valve control Limit values control PI temperature control 2-points temperature control | Master Switching Actuators Heating Actuators | MSA-810 SAE-810 / SAE-2410 SAE-816 DOE-825 HAE-805 |
| Phase dimmer (1 chan.) | Dimming Actuators | DAE-225 DBE-64 (DALI Bus) |
| Analog output PI temperature control | Analog Actuators | AAE-410 |
| Dimmer (1 chan.) RGB(W) dimmer (3-4 chan.) | Analog Actuators LED Actuators | AAE-410 LAE-802 |
| Tunable White (TW) dimmer (2 chan.) | LED Actuators | LAE-802 |
| Logic Gate Sequence Trigger Math | Virtual Logic modules | MSA-810 |
The actuator system is based on a master actuator, MSA-810, which includes 8 switching channels 10A. If additional channels are required, extension modules can be plugged in.
The switching functions described above are applicable to any switching channel, on the master or any of the switching extensions. Any supposable mixed form of switching outputs and shutter output is possible.
When configuring the actuator system, up to 8 extension modules can be added to the master. Each extension must be connected to the previous module using the left side connector. Extensions can only be used on the same row as the master actuator.
The following types of extensions are available :
General purpose switching channels :
High power switching channels:
Other types of extensions :
A maximum of 8 extensions can be connected behind the master actuator, which makes a potential of 72 outputs depending on the extensions used. Multiple master actuator systems can be used to extend the installation beyond these limits.
Switching outputs 10A are limited to maximum 40 channels on one master actuator. This includes the channels of the following modules:
Ex: 1 Master + 1 SAE-2410 + 1 SAE-810 = 40 channels 10A
All other types of extensions can be used in addition to a maximum of 8 extensions on a master.
Additional switching channels 16A can be used on the same master without limitation.
If additional channels 10A are required, a new master should be used.
CAUTION!
💡 A maximum of 40 switching channels 10A (Combined on MSA-810 / SAE-810 / SAE-2410) can be used in a single actuator system, for additional switching extensions prefer the use of low power extensions SAE-816.
Our support team is available to answer your technical questions.