Trigger

elausys · 17 september 2026
Op deze pagina

Triggercondities, uitgangstypen, vertragingen en configuratie van de weekkalender.

  • Integrated weekly calendar to trigger actions based on weekday and time
  • Evaluation of each input values based on fixed values or compared to second group object
  • Each input value is evaluated with the compared value according to the selection
    • Equal (=)
    • Greater than (>)
    • Less than (<)
    • Unequal (!=)
    • Greater or equal (>=)
    • Less or equal (<=)
    • Always true
  • Selectable logic between the 2 inputs: AND, OR, XOR, NAND, NOR, XNOR
  • Inputs type individually configurable from the following objects type
    • Switch - DPT 1.001
    • Scene - DPT 18.001
    • Percent value - DPT 5.001
    • 1-byte unsigned value (0-255) - DPT 5.005
    • 2-bytes unsigned - DPT 7.*
    • 2-bytes signed - DPT 8.*
    • 2-bytes float - DPT 9.*
    • 4-bytes unsigned - DPT 12.*
    • 4-bytes signed - DPT 13.*
    • 4-bytes float - DPT 14.*
  • Weekly calendar (week day, hour, minute)
  • Selection to send output value at any input change or only when output changes
  • Option to delay the output
  • Selection of output value from a fixed value or from input 1
  • Function output configurable from the following objects type
    • Switch - DPT 1.001
    • Scene - DPT 18.001
    • Percent value - DPT 5.001
    • RGB Color value - DPT 232.600
    • Tunable white value (Brightness & Temperature)
    • 1-byte unsigned value (0-255) - DPT 5.005
    • 2-bytes unsigned - DPT 7.*
    • 2-bytes signed - DPT 8.*
    • 2-bytes float - DPT 9.*
    • 4-bytes unsigned - DPT 12.*
    • 4-bytes signed - DPT 13.*
    • 4-bytes float - DPT 14.*

The channel can be blocked from the KNX bus using the “Block” communication object. When a channel is blocked, Input changes have no effect on the output.

Parameters

PARAMETERVALUESDESCRIPTION
Channel descriptionTextChannel description that is displayed in the channel menu and in the group objects name of this channel
Inputs evaluationInput 1 and 2 with fixed values Input 1 fixed and 2 with comparative object Input 1 with comparative object and 2 fixed Input 1 and 2 with comparative objectSelection of the inputs comparative values
Logic between input 1 and 2AND (default) OR XOR NAND NOR XNORSelection of the logic operation between input 1 and 2
Input x (1 to 2)
Input typeNot used (default) Switch - DPT 1.001 Scene - DPT 18.001 Percent value - DPT 5.001 1-byte unsigned value (0-255) - DPT 5.005 2-bytes unsigned - DPT 7. 2-bytes signed - DPT 8. 2-bytes float - DPT 9. 4-bytes unsigned - DPT 12. 4-bytes signed - DPT 13. 4-bytes float - DPT 14. Weekly calendarDatatype of the input value
Input conditionEqual (=) Greater than (>) Less than (<) Unequal (!=) Greater or equal (>=) Less or equal (<=) Always trueCondition to compare the input value with the compared value (from group object or fixed value)
Value0 (default) Value range based on the selected output type rangeValue to be compared with input value when a fixed value is selected for this input
Output
Output value sourceOutput fixed value (default) Value from input 1Selection if the output value is fixed or a copy of input 1 value.
Send output valueAt any input received (default) At input 1 received only At input 2 received only Once at valid output conditions Once at valid input 1 conditions only Once at valid input 2 conditions onlySelection if the output value is to be send on the bus at each change of the inputs or only once when the conditions become valid
Output typeNot used (default) Switch - DPT 1.001 Scene - DPT 18.001 Percent value - DPT 5.001 RGB Color value - DPT 232.600 Tunable white value (Brightness & Temperature) 1-byte unsigned value (0-255) - DPT 5.005 2-bytes unsigned - DPT 7. 2-bytes signed - DPT 8. 2-bytes float - DPT 9. 4-bytes unsigned - DPT 12. 4-bytes signed - DPT 13. 4-bytes float - DPT 14.Datatype of the value to be sent on the bus when the trigger is activated
Send value0 (default) Value range based on the selected output type rangeFixed value to be sent on the bus when trigger is activated
Output delay0 (default) 0..255Delay to send the output based on the “delay unit” parameter.
Delay unit100ms seconds (default) minutesDelay units for the output delay value.

Communication objects

NRNAMEFUNCTIONSIZEFLAGSTYPE
1BlockOn/Off1 bitCRW1.003 - enable
3 *Input 1 - SwitchTrue/False1 bitCW1.001 - switch
4 *Input 1 – Compared valueTrue/False1 bitCW1.001 - switch
5 *Input 2 - SwitchTrue/False1 bitCW1.001 - switch
6 *Input 2 – Compared valueTrue/False1 bitCW1.001 - switch
7Output - SwitchPercent1 bitCRT5.001 - percentage
8Output - BrightnessPercent1 byteCRT5.001 - percentage
  • Depending on the chosen datatype for the inputs, these group objects can have the following configurations:
NAMEFUNCTIONSIZEFLAGSTYPE
Input x - SwitchTrue/False1 bitCW1.001 – switch
Input x - SceneScene1 byteCW18.001 – Scene control
Input x - PercentPercent1 byteCW5.001 – percentage
Input x - Value1 byte1 byteCW5.005 – 1-byte unsigned
Input x - Value2 bytes2 bytesCW7.x – 2-bytes unsigned
Input x - Value2 bytes2 bytesCW8.x – 2 bytes signed
Input x - Value2 bytes2 bytesCW9.x – 2 bytes float
Input x - Value4 bytes4 bytesCW12.x – 4-bytes unsigned
Input x - Value4 bytes4 bytesCW13.x – 4 bytes signed
Input x - Value4 bytes4 bytesCW14.x – 4 bytes float

__ Depending on the chosen datatype for the output, this group object can have the following configurations:

NAMEFUNCTIONSIZEFLAGSTYPE
Output - SwitchTrue/False1 bitCRT1.001 – switch
Output - SceneScene1 byteCRT18.001 – Scene control
Output - PercentPercent1 byteCRT5.001 – percentage
Output - RGBRGB3 bytesCRT232.600 – RGB value
Output - TemperaturePercent1 byteCRT5.001 – percentage
Output - Value1 byte1 byteCRT5.005 – 1-byte unsigned
Output - Value2 bytes2 bytesCRT7.x – 2-bytes unsigned
Output - Value2 bytes2 bytesCRT8.x – 2 bytes signed
Output - Value2 bytes2 bytesCRT9.x – 2 bytes float
Output - Value4 bytes4 bytesCRT12.x – 4-bytes unsigned
Output - Value4 bytes4 bytesCRT13.x – 4 bytes signed
Output - Value4 bytes4 bytesCRT14.x – 4 bytes float

Manual navigation

All manual articles

Veelgestelde vragen

Wat moet worden gecontroleerd voor een trigger van de weekkalender?

Controleer de gekozen weekdag en tijd en de datum-, tijd- en broninstellingen van het hostapparaat.

Wat moet worden gecontroleerd als een trigger geen uitgang oplevert?

Controleer actieve voorwaarden, invoerwaarden, groepsadressen, de Block-status, uitgangsvertraging en het geconfigureerde uitgangstype.