Saltar para o conteúdo
Elausys

Atuadores KNX / Manual do Utilizador do Módulo Lógico

Funções matemáticas

Operações matemáticas, tipos de dados de entrada, valores fixos e comportamento de envio da saída.

elausys · 18 setembro 2026
Nesta página

Função matemática

Operações matemáticas, tipos de dados de entrada, valores fixos e comportamento de envio da saída.

A função suporta as seguintes operações:

  • Selectable mathematical operation
    • Addition (+)
    • Subtraction (-)
    • Multiplication (*)
    • Division (/)
    • Minimum of two inputs
    • Maximum of two inputs
    • Average of two inputs
  • Selectable Input 2 value from a fixed value or from a group object
  • Inputs type configurable from the following objects type
    • Percent value - DPT 5.001
    • 1-byte unsigned value (0-255) - DPT 5.005
    • 2-bytes unsigned - DPT 7.*
    • 2-bytes signed - DPT 8.*
    • 2-bytes float - DPT 9.*
    • 4-bytes unsigned - DPT 12.*
    • 4-bytes signed - DPT 13.*
    • 4-bytes float - DPT 14.*
  • Selection to send output value at any input change or only when output changes
  • Option to delay the output

The channel can be blocked from the KNX bus using the “Block” communication object. When a channel is blocked, Input changes have no effect on the output.

Parameters

PARAMETERVALUESDESCRIPTION
Channel descriptionTextChannel description that is displayed in the channel menu and in the group objects name of this channel
OperationAddition (+) Subtraction (-) Multiplication (*) Division (/) Minimum of two inputs Maximum of two inputs Average of two inputsSelection of the mathematical operation to perform between the two inputs values
Objects typePercent value - DPT 5.001 1-byte unsigned value (0-255) - DPT 5.005 (default) 2-bytes unsigned - DPT 7. 2-bytes signed - DPT 8. 2-bytes float - DPT 9. 4-bytes unsigned - DPT 12. 4-bytes signed - DPT 13. 4-bytes float - DPT 14.Datatype of the inputs value
Send conditionAt any input change (default) At output changeSelection if the output value is to be send on the bus at each change of the inputs or only when the output changes
Type of input 2Objects (default) Fixed valueSelection if input 2 value is received from a group object or set as a fixed value
Value0 (default) Value range based on the selected objects type rangeValue of input 2 if a fixed value is selected for this input
Output
Output delay0 (default) 0..255Delay to send the output based on the “delay unit” parameter.
Delay unit100ms seconds (default) minutesDelay units for the output delay value.

Communication objects

NRNAMEFUNCTIONSIZEFLAGSTYPE
1BlockOn/Off1 bitCRW1.003 - enable
3 *Input 1 – ValuePercent1 bitCW5.001 - percentage
5 *Input 2 – ValuePercent1 bitCW5.001 - percentage
7 *Output – ValuePercent1 bitCRT5.001 - percentage
  • Depending on the chosen datatype for the objects, these group objects can have the following configurations:
NAMEFUNCTIONSIZEFLAGSTYPE
Input x /Output - PercentPercent1 byteCW5.001 – percentage
Input x /Output - Value1 byte1 byteCW5.005 – 1-byte unsigned
Input x /Output - Value2 bytes2 bytesCW7.x – 2-bytes unsigned
Input x /Output - Value2 bytes2 bytesCW8.x – 2 bytes signed
Input x /Output - Value2 bytes2 bytesCW9.x – 2 bytes float
Input x /Output - Value4 bytes4 bytesCW12.x – 4-bytes unsigned
Input x /Output - Value4 bytes4 bytesCW13.x – 4 bytes signed
Input x /Output - Value4 bytes4 bytesCW14.x – 4 bytes float

Manual navigation

All manual articles

Perguntas frequentes

A segunda entrada pode ser um valor fixo?

Sim. Defina Type of input 2 como Fixed value e introduza um valor dentro do intervalo do tipo de dados selecionado.

Que operações estão disponíveis?

Estão disponíveis adição, subtração, multiplicação, divisão, mínimo, máximo e média das duas entradas.

Continuar a explorar

Encontre os outros guias deste produto na documentação.

Voltar a Manual do Utilizador do Módulo Lógico