Protocolo Modbus TCP

Códigos de função suportados, respostas de exceção e cabeçalho das mensagens Modbus TCP.

elausys · 15 setembro 2026
Nesta página

Supported Function Codes

The gateway supports the following Modbus function codes:

CodeNameDescription
0x01Read CoilsRead coil status (status registers)
0x05Write Single CoilWrite a single coil (command registers)

Exception Codes

The gateway returns the following Modbus exception codes when an error occurs:

CodeNameDescription
0x01Illegal FunctionFunction code not supported
0x02Illegal Data AddressCoil address out of range
0x03Illegal Data ValueInvalid value (neither 0xFF00 nor 0x0000)

MBAP Header

All Modbus TCP communication uses the standard MBAP (Modbus Application Protocol) header:

ByteFieldValue
0–1Transaction IDSet by client (echoed in response)
2–3Protocol ID0x0000 (Modbus)
4–5LengthNumber of following bytes
6Unit ID0x01
7Function Code0x01, 0x05
8+DataFunction-specific payload

Perguntas frequentes

Que códigos de função Modbus são suportados?

Use 0x01, Read Coils, e 0x05, Write Single Coil. A gateway disponibiliza coils e não holding registers.

Que valores são válidos para Write Single Coil?

Os valores documentados são 0xFF00 para ON e 0x0000 para OFF. Outros valores devolvem a exceção 0x03, Illegal Data Value.

Que Unit ID deve constar no cabeçalho MBAP?

Defina a Unit ID como 0x01, o valor decimal 1.