Webkonfiguration des Gateways
[object Object]
| Connection | Mode | Gateway Modbus settings |
|---|---|---|
| SUN2000 via SmartDongle | Connect | Server IP: SmartDongle IP |
Server Port: 502
Unit ID: 1 | | EMMA | Connect | Server IP: EMMA IP
Server Port: 502
Unit ID: 0 | | SUN2000L | Listen | Server Port: 502 Unit ID: 0 |
Verbindungsprüfung
Prüfen Sie nach der Einstellung von Anwendungsmodell und Kommunikationsparametern, ob die Connected-LED leuchtet. Die Network-LED bestätigt nur die physische Ethernetverbindung, nicht gültige Wechselrichterdaten auf KNX.
Huawei konfigurieren
SUN2000 Series using a SmartDongle:
From the Fusion Solar portal, verify that the SmartDongle software version is >= SPC120.
If the software version is not up to date, there are two ways to perform the firmware upgrade:
- Local via APP
You can download the latest version from Huawei homepage.
https://support.huawei.com/enterprise/en/digital-power/sdongle-pid-23826585/software
- Upgrade via Portal:
Plants > Upgrade Management > Add
Select Device type: Smart Dongle > SPC 120 and Device
In the FusionSolar application, modbus should be enabled:
EMMA-Verbindung einrichten
- Connection of the EMMA must be via LAN, as WLAN does not work:
- Open the Fusion Solar App with installer credentials
- Go to Connect EMMA > Communication configuration > Router configuration
- Select LAN
- For the physical LAN connection, use the WAN port on the EMMA, NOT the LAN port.
- Ensure the Gateway is in the same (V)LAN as the EMMA.
- Activate Modbus on EMMA:
- Via the Fusion Solar app with the installer credentials
- Navigate to Services > "Commissioning the device" in the Settings
- Go to Communication configuration
- Enable Modbus TCP connection
- Turn TLS off
- Set the Elausys GATEWAY address as the client IP address
SUN2000L-Verbindung einrichten
The following procedure applies to SUN2000L inverters.
Install the Huawei mobile application “FusionHome” on your smartphone.
If your inverter is not yet connected to the WIFI network, follow the instructions from the video below :
In the application, select your inverter and login using the installer code. Default code is 00000a
From the home page choose “Communication configuration”, set the management system connection parameters:
- Set at domain name: IP address of the KNX gateway
- Assure that the port is 502 and encrypted transmission is disabled.
- After you set the domain name and the port, press “Connect”
- Check that the connection with the KNX gateway is established on the front panel of the KNX gateway, the status LED “Connected” should be ON.