Zum Inhalt springen
Elausys

Modbus TCP-Gateways für Alarmsysteme / AJAX-MBTCP Benutzerhandbuch

Coil-Übersicht

Vollständige Adressübersicht für Bereichs- und globale Befehle, Alarmzustände, Detektoren und Stromversorgungsfehler.

elausys · 16 September 2026
Auf dieser Seite

Overview

All data is mapped to Modbus coils (single-bit registers). The complete coil address space is organized as follows:

Address RangeCountTypeDescription
0x0000 – 0x00078Command (R/W)Arm / Disarm per area (4 areas × 2)
0x0008 – 0x000A3Command (R/W)Global Arm / Disarm / Partial
0x000B – 0x002E36Status (R)Area status (4 areas × 9)
0x002F – 0x008E96Status (R)Detector status (96 detectors)
0x008F – 0x00902Status (R)System status (AC, Battery)
Total145

Area Command Coils (0x0000 – 0x0007)

These coils allow arming and disarming individual areas. Commands are pulse-type: only the ON edge triggers the action. Coils are automatically reset to 0 after execution.

AddressAreaAction
0x0000Area 1Arm
0x0001Area 1Disarm
0x0002Area 2Arm
0x0003Area 2Disarm
0x0004Area 3Arm
0x0005Area 3Disarm
0x0006Area 4Arm
0x0007Area 4Disarm

Note: When Partition Mode is OFF (global hub mode), only Area 1 coils are active. Use the global command coils for simplified operation.

Global Command Coils (0x0008 – 0x000A)

These coils provide system-wide control commands:

AddressCommandDescription
0x0008Global ArmArm all areas
0x0009Global DisarmDisarm all areas
0x000AGlobal PartialNight Mode (ON = activate, OFF = deactivate)

Behaviour with Partition OFF (global hub mode)

The three states are mutually exclusive (Armed / Disarmed / Partial). Only the ON edge triggers the action. All commands target the hub globally.

Behaviour with Partition ON (group mode)

  • Global Arm: sends an arm command to each configured area individually.
  • Global Disarm: sends a disarm command to each configured area and deactivates Night Mode.
  • Global Partial: always operates at hub level to activate or deactivate Night Mode.

Area Status Coils (0x000B – 0x002E) — Read Only

Each area has 9 status coils. With 4 areas, this gives 36 status coils in total. A coil value of ON (1) indicates the status is active.

Status Bit Layout per Area

OffsetStatusDescription
+0DisarmedArea is disarmed and ready
+1Not used
+2Not used
+3ArmedArea is armed (total mode)
+4Partial ArmedNight mode / partial arm active
+5FireFire alarm active
+6Not used
+7PanicPanic alarm active
+8IntrusionIntrusion alarm active

Detailed Address Map

AreaDisarmed--ArmedPartialFire-PanicIntrusion
Area 10x000B0x000C0x000D0x000E0x000F0x00100x00110x00120x0013
Area 20x00140x00150x00160x00170x00180x00190x001A0x001B0x001C
Area 30x001D0x001E0x001F0x00200x00210x00220x00230x00240x0025
Area 40x00260x00270x00280x00290x002A0x002B0x002C0x002D0x002E

Detector Status Coils (0x002F – 0x008E) — Read Only

Each detector is mapped to a single coil, supporting up to 96 detectors per gateway. A coil value of ON (1) indicates an alarm or fault condition; OFF (0) indicates normal operation.

AddressDetector
0x002FDetector 1
0x0030Detector 2
......
0x008EDetector 96

Remember that detector statuses are only reported when the system is armed, in night mode, or when individual devices are set to Always Active in the AJAX app (see Zone Reporting Behaviour under Configuring the alarm system).

System Status Coils (0x008F – 0x0090) — Read Only

These coils report the power supply status of the AJAX alarm system. A coil value of ON (1) indicates a fault condition.

AddressStatusDescription
0x008FAC FaultMain power supply failure
0x0090Battery FaultBattery low or failure

Häufig gestellte Fragen

Welche Coils kann ich beschreiben?

Nur Befehls-Coils von 0x0000 bis 0x000A akzeptieren Schreibvorgänge. Bereichs-, Detektor- und Systemstatus-Coils sind schreibgeschützt.

Wie funktionieren einzelne Scharf- und Unscharfbefehle für Bereiche?

Schreiben Sie ON in den betreffenden Befehls-Coil. Nur die ON-Flanke löst die Aktion aus; danach wird der Befehls-Coil auf 0 zurückgesetzt.

Was macht Global Disarm bei aktiviertem Partition Mode?

Der Befehl sendet an jeden konfigurierten Bereich einen Unscharfbefehl und deaktiviert Night Mode. Nur eine Gruppe unscharf zu schalten deaktiviert Night Mode nicht.

Wo kann ich Detektor- und Stromversorgungsfehler lesen?

Detektorstatus-Coils liegen von 0x002F bis 0x008E. AC Fault ist 0x008F und Battery Fault ist 0x0090.

Weiter erkunden

Finden Sie die weiteren Anleitungen zu diesem Produkt in der Dokumentation.

Zurück zu AJAX-MBTCP Benutzerhandbuch