Modbus TCP-Gateways für Alarmsysteme / AJAX-MBTCP Benutzerhandbuch

Fehlerbehebung und häufige Fehler

Beheben Sie fehlende Detektoraktualisierungen, Steuerungsfehler, Zeitüberschreitungen und ungültige Coil-Schreibvorgänge.

elausys · 17 September 2026
Auf dieser Seite

Not understanding zone reporting behaviour

AJAX sensors only report zone status through Modbus TCP when the system is armed or in night mode. Setting devices to Always Active enables daytime reporting, but also means those zones will trigger the alarm when the system is disarmed. Plan which zones genuinely need 24/7 Modbus TCP reporting.

Not inviting Elausys as Security Company

Area control (arm/disarm from Modbus TCP) will not work without inviting Elausys as a Security Company in the AJAX app. Internet access is also required for arming/disarming commands.

Incorrect area count with AJAX groups

Match Partition Mode and the number of areas on the gateway web interface to the AJAX group configuration. Check these settings if individual group commands behave incorrectly.

Expecting disarm to exit Night Mode

Disarming a group does not disable Night Mode when groups are enabled. You must explicitly send a Partial Arm (OFF) command to disable Night Mode. Design your controller logic to handle this independently.

Ethernet connection loss

If the Ethernet connection between the gateway and the AJAX Hub drops, the Connected LED will turn off. Detector status coils will hold their last known state until communication is restored.

Modbus TCP connection timeout

The gateway automatically closes idle Modbus TCP connections after 60 seconds of inactivity. Ensure your Modbus master is configured with a polling interval shorter than 60 seconds to maintain the connection.

Writing to read-only coils

Attempting to write to status coils (addresses 0x000B and above) will return a Modbus exception code 0x02 (Illegal Data Address). Only command coils (0x0000–0x000A) accept write operations.

Häufig gestellte Fragen

Beweist ein angezeigter Detektorstatus, dass die Kommunikation funktioniert?

Nein. Detektorstatus behalten nach Kommunikationsverlust den zuletzt bekannten Zustand. Prüfen Sie Connected-LED und Kommunikationsweg, bevor Sie einem angezeigten Wert vertrauen.

Ändert Always Active nur die Statusanzeige?

Nein. Der Detektor kann damit auch bei unscharfem System einen Alarm auslösen. Verwenden Sie diese Option nur, wenn dieses Verhalten vorgesehen ist.