All data is mapped to Modbus coils (single-bit registers). The complete coil address space is organized as follows:

Address RangeCountTypeDescription
0x0000 – 0x00078Command (R/W)Arm / Disarm per area (4 areas × 2)
0x0008 – 0x000A3Command (R/W)Global Arm / Disarm / Partial
0x000B – 0x002E36Status (R)Area status (4 areas × 9)
0x002F – 0x008E96Status (R)Detector status (96 detectors)
0x008F – 0x00902Status (R)System status (AC, Battery)
Total145

Area Command Coils (0x0000 – 0x0007)

These coils allow arming and disarming individual areas. Commands are pulse-type: only the ON edge triggers the action. Coils are automatically reset to 0 after execution.

AddressAreaAction
0x0000Area 1Arm
0x0001Area 1Disarm
0x0002Area 2Arm
0x0003Area 2Disarm
0x0004Area 3Arm
0x0005Area 3Disarm
0x0006Area 4Arm
0x0007Area 4Disarm

Note: When Partition Mode is OFF (global hub mode), only Area 1 coils are active. Use the global command coils for simplified operation.

Global Command Coils (0x0008 – 0x000A)

These coils provide system-wide control commands:

AddressCommandDescription
0x0008Global ArmArm all areas
0x0009Global DisarmDisarm all areas
0x000AGlobal PartialNight Mode (ON = activate, OFF = deactivate)

Behaviour with Partition OFF (global hub mode)

The three states are mutually exclusive (Armed / Disarmed / Partial). Only the ON edge triggers the action. All commands target the hub globally.

Behaviour with Partition ON (group mode)

  • Global Arm: sends an arm command to each configured area individually.
  • Global Disarm: sends a disarm command to each configured area and deactivates Night Mode.
  • Global Partial: always operates at hub level to activate or deactivate Night Mode.

Area Status Coils (0x000B – 0x002E) — Read Only

Each area has 9 status coils. With 4 areas, this gives 36 status coils in total. A coil value of ON (1) indicates the status is active.

Status Bit Layout per Area

OffsetStatusDescription
+0DisarmedArea is disarmed and ready
+1Not used
+2Not used
+3ArmedArea is armed (total mode)
+4Partial ArmedNight mode / partial arm active
+5FireFire alarm active
+6Not used
+7PanicPanic alarm active
+8IntrusionIntrusion alarm active

Detailed Address Map

AreaDisarmed--ArmedPartialFire-PanicIntrusion
Area 10x000B0x000C0x000D0x000E0x000F0x00100x00110x00120x0013
Area 20x00140x00150x00160x00170x00180x00190x001A0x001B0x001C
Area 30x001D0x001E0x001F0x00200x00210x00220x00230x00240x0025
Area 40x00260x00270x00280x00290x002A0x002B0x002C0x002D0x002E

Detector Status Coils (0x002F – 0x008E) — Read Only

Each detector is mapped to a single coil, supporting up to 96 detectors per gateway. A coil value of ON (1) indicates an alarm or fault condition; OFF (0) indicates normal operation.

AddressDetector
0x002FDetector 1
0x0030Detector 2
......
0x008EDetector 96

Remember that detector statuses are only reported when the system is armed, in night mode, or when individual devices are set to Always Active in the AJAX app (see Zone Reporting Behaviour under Configuring the alarm system).

System Status Coils (0x008F – 0x0090) — Read Only

These coils report the power supply status of the AJAX alarm system. A coil value of ON (1) indicates a fault condition.

AddressStatusDescription
0x008FAC FaultMain power supply failure
0x0090Battery FaultBattery low or failure

Συχνές ερωτήσεις

Ποια coils μπορώ να γράψω;

Μόνο τα coils εντολών 0x0000 έως 0x000A δέχονται εγγραφές. Τα coils κατάστασης περιοχής, ανιχνευτή και συστήματος είναι μόνο για ανάγνωση.

Πώς λειτουργούν οι μεμονωμένες εντολές όπλισης και αφόπλισης περιοχής;

Γράψτε ON στο αντίστοιχο coil εντολής. Μόνο το μέτωπο ON ενεργοποιεί την ενέργεια και το coil επανέρχεται στο 0 μετά την εκτέλεση.

Τι κάνει το Global Disarm όταν το Partition Mode είναι ενεργό;

Στέλνει εντολή αφόπλισης σε κάθε ρυθμισμένη περιοχή και απενεργοποιεί το Night Mode. Η αφόπλιση μίας μόνο ομάδας δεν απενεργοποιεί το Night Mode.

Πού μπορώ να διαβάσω καταστάσεις ανιχνευτών και βλαβών τροφοδοσίας;

Τα coils κατάστασης ανιχνευτών είναι από 0x002F έως 0x008E. Το AC Fault είναι 0x008F και το Battery Fault 0x0090.