Passer au contenu
Elausys

Passerelles KNX pour onduleurs / Manuel d'utilisation INV-KNX Kostal

Matériel et compatibilité

Schémas de raccordement, voyants du panneau avant et limites de compatibilité pour INV-KNX Kostal.

elausys · 11 septembre 2026
Sur cette page

8.1 System AC and PV values

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String).

GOObject nameSizeDPT and typeSignification and availability
1Module status1 byte20.011
DPT_ErrorClass_System
Sends 0 when the module is operating normally, sends an error code when applicable.
2Firmware version14 bytes16.000
Character string
Returns the firmware version of the device when the object is read.
3AC Current4 bytes14.019
Electric current (A)
AC Total Current value
4AC Current A4 bytes14.019
Electric current (A)
AC Current phase A
5AC Current B4 bytes14.019
Electric current (A)
AC Current phase B
6AC Current C4 bytes14.019
Electric current (A)
AC Current phase C
7AC Voltage4 bytes14.027
Electric potential (V)
AC Total Voltage
8AC Voltage AB4 bytes14.027
Electric potential (V)
AC Voltage phase AB (NOT USED)
9AC Voltage BC4 bytes14.027
Electric potential (V)
AC Voltage phase BC (NOT USED)
10AC Voltage CA4 bytes14.027
Electric potential (V)
AC Voltage phase CA (NOT USED)
11AC Voltage AN4 bytes14.027
Electric potential (V)
AC Voltage phase AN
12AC Voltage BN4 bytes14.027
Electric potential (V)
AC Voltage phase BN
13AC Voltage CN4 bytes14.027
Electric potential (V)
AC Voltage phase CN
14DC Current4 bytes14.019
Electric current (A)
DC Total Current value (NOT USED)
15DC Voltage4 bytes14.027
Electric potential (V)
DC Total Voltage (NOT USED)
16PV1 Voltage4 bytes14.027
Electric potential (V)
PV1 Voltage
17PV1 Current4 bytes14.019
Electric current (A)
PV1 Current
18PV2 Voltage4 bytes14.027
Electric potential (V)
PV2 Voltage
19PV2 Current4 bytes14.019
Electric current (A)
PV2 Current

8.2 Power energy and diagnostics

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String).

GOObject nameSizeDPT and typeSignification and availability
20PV3 Voltage4 bytes14.027
Electric potential (V)
PV3 Voltage
21PV3 Current4 bytes14.019
Electric current (A)
PV3 Current
22PV4 Voltage4 bytes14.027
Electric potential (V)
PV4 Voltage (NOT USED)
23PV4 Current4 bytes14.019
Electric current (A)
PV4 Current (NOT USED)
24AC Power4 bytes14.056
Power (W)
AC Power
25DC Power4 bytes14.056
Power (W)
DC Power
26AC Frequency4 bytes14.033
Frequency (Hz)
AC Frequency
27AC VA4 bytes14.056
Power (W)
AC Apparent power
28AC VAR4 bytes14.056
Power (W)
AC Reactive power
29AC PF4 bytes14.057
Power factor (cos phi)
Power factor
30AC Energy4 bytes13.013
Active energy (kWh)
Total AC Energy
31Efficiency2 bytes8.010
Percentage (%)
Inverter efficiency (NOT USED)
32Insulation4 bytes14.056
Resistance (Ohm)
Insulation resistance
33Temperature2 bytes9.001
Temperature (°C)
Cabinet temperature
40Daily Energy Yield4 bytes13.013
Energy (kWh)
Daily energy

8.3 Battery and grid values

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String).

GOObject nameSizeDPT and typeSignification and availability
41Battery 1 Running Status2 bytes-
-
(NOT USED)
42Battery 1 power4 bytes14.056
Power (W)
Battery charging/discharging power
43Battery 1 SOC1 byte5.001
Percentage (%)
Battery state of charge
44Battery 1 current day charge4 bytes13.013
Energy (kWh)
(NOT USED)
45Battery 1 current day discharge4 bytes13.013
Energy (kWh)
(NOT USED)
46Battery 1 total charge4 bytes13.013
Energy (kWh)
Total battery charge
47Battery 1 total discharge4 bytes13.013
Energy (kWh)
Total battery discharge
48Battery 2 Running Status2 bytes-
-
(NOT USED)
49Battery 2 power4 bytes14.056
Power (W)
(NOT USED)
50Battery 2 SOC1 byte5.001
Percentage (%)
(NOT USED)
51Battery 2 current day charge4 bytes13.013
Energy (kWh)
(NOT USED)
52Battery 2 current day discharge4 bytes13.013
Energy (kWh)
(NOT USED)
53Battery 2 total charge4 bytes13.013
Energy (kWh)
(NOT USED)
54Battery 2 total discharge4 bytes13.013
Energy (kWh)
(NOT USED)
55Powermeter4 bytes14.056
Power (W)
> 0: charging < 0: discharging

Enable the corresponding equipment parameters in ETS. A dash in the DPT column indicates that no standard datatype is specified. NOT USED entries remain unavailable.

Tous les chapitres du manuel utilisateur INV-KNX Kostal

Questions fréquentes

Où se trouvent les raccordements de la passerelle ?

Le raccordement du bus KNX se trouve en haut. L’alimentation auxiliaire 12–30 VDC et la connexion Ethernet RJ45 se trouvent en bas.

Quelle est la différence entre les LED Network et Connected ?

Network indique une connexion Ethernet physique. Connected indique la communication avec l’onduleur.

Quelle interface l’onduleur Kostal doit-il prendre en charge ?

L’onduleur doit prendre en charge l’interface SunSpec Modbus et se connecter au même réseau Ethernet/routeur que la passerelle KNX.

Continuer l'exploration

Retrouvez les autres guides de ce produit dans la documentation.

Retour à Manuel d'utilisation INV-KNX Kostal