Gateway Modbus TCP per Sistemi di Allerta / Manuale utente AJAX-MBTCP

Risoluzione dei problemi ed errori comuni

Risolvi aggiornamenti mancanti dei rilevatori, errori di controllo, timeout e scritture di coil non valide.

elausys · 17 settembre 2026
In questa pagina

Not understanding zone reporting behaviour

AJAX sensors only report zone status through Modbus TCP when the system is armed or in night mode. Setting devices to Always Active enables daytime reporting, but also means those zones will trigger the alarm when the system is disarmed. Plan which zones genuinely need 24/7 Modbus TCP reporting.

Not inviting Elausys as Security Company

Area control (arm/disarm from Modbus TCP) will not work without inviting Elausys as a Security Company in the AJAX app. Internet access is also required for arming/disarming commands.

Incorrect area count with AJAX groups

Match Partition Mode and the number of areas on the gateway web interface to the AJAX group configuration. Check these settings if individual group commands behave incorrectly.

Expecting disarm to exit Night Mode

Disarming a group does not disable Night Mode when groups are enabled. You must explicitly send a Partial Arm (OFF) command to disable Night Mode. Design your controller logic to handle this independently.

Ethernet connection loss

If the Ethernet connection between the gateway and the AJAX Hub drops, the Connected LED will turn off. Detector status coils will hold their last known state until communication is restored.

Modbus TCP connection timeout

The gateway automatically closes idle Modbus TCP connections after 60 seconds of inactivity. Ensure your Modbus master is configured with a polling interval shorter than 60 seconds to maintain the connection.

Writing to read-only coils

Attempting to write to status coils (addresses 0x000B and above) will return a Modbus exception code 0x02 (Illegal Data Address). Only command coils (0x0000–0x000A) accept write operations.

Domande frequenti

Uno stato del rilevatore visualizzato dimostra che la comunicazione funziona?

No. Gli stati mantengono l'ultimo valore noto dopo una perdita di comunicazione. Controlla il LED Connected e il percorso di comunicazione prima di affidarti al valore.

Always Active modifica solo la visualizzazione dello stato?

No. Consente anche al rilevatore di attivare un allarme quando il sistema è disinserito. Usa questa opzione solo se il comportamento è previsto.

Continua a esplorare

Trova le altre guide per questo prodotto nella documentazione.

Torna a Manuale utente AJAX-MBTCP