KNX Gateways voor Omvormers / INV-KNX Fronius Gebruikershandleiding

Snelle inbedrijfstelling

De inbedrijfstellingsprocedure voor INV-KNX Fronius, van bekabeling tot gevalideerde KNX-metingen.

elausys · 10 september 2026
Op deze pagina

Follow these steps in order. Use the detailed sections for model-specific settings and the complete object reference.

1 De installatie voorbereiden

Have the gateway, KNX bus connection, 12-30 VDC auxiliary supply, network connection, ETS application and inverter configuration access ready. Check compatibility and firmware in Sections 3 and 10.

2 De gateway aansluiten en voeden

Connect KNX at the top. Connect auxiliary power and RJ45 Ethernet at the bottom. Connect the equipment to the same local network. The green Network LED confirms the Ethernet link; see Section 3.

3 De omvormerverbinding configureren

Enable Modbus TCP or configure the required inverter connection using Section 4. Confirm the inverter address, port and Unit ID.

4 Het gatewaynetwerk en de Modbusverbinding instellen

Open 192.168.1.51 from a laptop on a compatible network and assign an appropriate fixed gateway IP address. Set Mode to Connect, Server IP to the inverter address, Server Port to 502 and Unit ID to 1.

5 Het KNX-apparaat in ETS configureren

Assign a free physical address. Set Inverter model to 3 for Fronius including Gen24; 6 for Fronius Symo Hybrid. Set the AC network, applicable PV circuits, refresh rate and available equipment. Set Device Options to the Fronius Smart Meter Modbus ID when a meter is installed; check the actual ID (default 200 or 240). See Sections 5 and 6.

6 Groepsadressen koppelen en downloaden

Assign group addresses to the required objects. Press P when ETS requires programming mode and perform a full application download for initial commissioning. See Section 5.

7 Gegevens valideren en logica inschakelen

Check the Connected LED and Module status (GO 1 = 0). Read firmware (GO 2), wait for the polling interval and compare live values with the inverter. Check power directions and optional equipment before enabling logic. See Section 7.

Commissioning is complete when

The network and inverter links are established, the ETS download succeeds, and the required group objects return plausible values for the installed equipment.

All chapters of the INV-KNX Fronius user manual

Veelgestelde vragen

Wat moet klaar zijn vóór de inbedrijfstelling?

Bereid de gateway, 12–30 VDC-hulpvoeding, KNX-bus, netwerkaansluitingen, de juiste ETS-applicatie en toegang tot de omvormerconfiguratie voor.

Bewijst de Network-led dat de inbedrijfstelling voltooid is?

Nee. De Network-led bevestigt de fysieke Ethernetverbinding. Controleer Connected, voltooi de ETS-download en vergelijk de KNX-waarden met de omvormer.

Wanneer moet ik automatisering op basis van omvormergegevens inschakelen?

Controleer de modulestatus, wacht het pollinginterval af, vergelijk live metingen en controleer vermogensrichtingen en optionele apparatuur.

Verder verkennen

Vind de andere handleidingen voor dit product in de documentatie.

Terug naar INV-KNX Fronius Gebruikershandleiding