Gateway web configuration

The factory gateway IP address is 192.168.1.51. Connect a laptop that can reach this address and open it in a web browser. If the page is unreachable, check the Ethernet link, the laptop network settings and whether the gateway already has a different IP address.

Assign the gateway a free fixed IP address suitable for the installation. Record it and reconnect at the new address after applying the network change.

SettingValue
ModeConnect
IP / server addressIP address of the SMA inverter
Server Port502, or the matching TCP port configured on the inverter
Unit Id3 with model 23; 126 with model 1

Always connect to the inverter IP address. Do not use the Sunny Home Manager IP address. A Sunny Home Manager is not required for model 23. Grid power comes from the inverter’s grid-metering registers, which depend on an installed SMA Energy Meter or Sunny Home Manager. Without this metering source, grid power may be zero or unavailable.

Enable the SMA TCP server in Sunny Explorer

Use this procedure on inverters configured through Sunny Explorer. Create a Speedwire system as described in the Sunny Explorer user manual. For a different inverter interface, use the corresponding SMA instructions to enable the same Modbus TCP server settings.

  1. Start Sunny Explorer and open or create the Speedwire system.
  2. Log into the system as Installer.
  3. Select the SMA inverter in the system tree.
  4. Open Settings, then External Communication.
  5. Select Edit. Under Modbus, locate TCP Server.
  6. Set Modbus > TCP Server > Activated to Yes.
  7. Keep port 502, or set a different port and enter the same port in the gateway.
  8. Select Save.

Connection check

After configuring the model and Unit Id, check that the Connected LED is on. A Network LED alone confirms only the physical Ethernet link. It does not confirm Modbus communication or valid KNX data.

Manual navigation

All chapters of the INV-KNX SMA user manual

Häufig gestellte Fragen

Wie lautet die werkseitige IP-Adresse des Gateways?

Die werkseitige Adresse lautet 192.168.1.51. Verwenden Sie einen Laptop, der diese Adresse erreicht, vergeben Sie eine freie feste IP-Adresse und verbinden Sie sich erneut über die neue Adresse.

Welche Modbus-Verbindungseinstellungen soll ich verwenden?

Verwenden Sie den Modus Connect und die IP-Adresse des Wechselrichters. Stellen Sie Port 502 oder den konfigurierten TCP-Port des Wechselrichters ein. Verwenden Sie Unit Id 3 mit Modell 23 oder 126 mit Modell 1. Richten Sie die Verbindung nicht auf Sunny Home Manager.