A group object (GO) is a device datapoint. A group address (GA) links it to other KNX devices or a visualisation. Assign group addresses only to the objects needed by the project and match their datatypes to Section 8.
Contrôles de mise en service
| GO | Object | What to check |
|---|---|---|
| 1 | Module status | 0 means normal operation; investigate a non-zero status. |
| 2 | Firmware version | Read the version and check the applicability in Section 11. |
| 24 | AC Power | Compare the value with the inverter display or application. |
| 30 | AC Energy | Compare the accumulated value and units. |
| 42 / 43 | Battery power / SOC | Where supported, enable Battery 1 and compare with the battery state. |
| 55 | Powermeter | Where supported, enable the meter and verify the measurement direction. |
Vérifier les sens de puissance et la disponibilité
GO 40 Daily Energy Yield: (NOT USED)
GO 41 Battery 1 Running Status: 0: OFF 1: EMPTY 6: DISCHARGING 7: CHARGING 9: FULL 10: HOLDING 11: TESTING
GO 42 Battery 1 power: (NOT USED)
GO 49 Battery 2 power: (NOT USED)
GO 55 Powermeter: Fronius Smart meter (meter modbus ID must be set in the ETS parameter Options)
Objets indisponibles
Objects marked NOT USED are unavailable for this application even when the generic ETS interface exposes them. Check equipment and operating conditions before treating zero values as a fault.