KNX Gateways voor Omvormers / INV-KNX SMA Gebruikershandleiding

Groepsadressen en gegevensvalidatie

Commissioning checks and interpretation of KNX measurements supplied by INV-KNX Fronius.

elausys · 15 september 2026
Op deze pagina

A group object (GO) is a device datapoint. A group address (GA) links that object to other devices or a visualisation in the KNX project. Assign a GA only to the objects required by the application.

Suggested commissioning test set

GOObjectWhat to check
1Module status0 means normal operation; a non-zero value is an error code.
2Firmware versionRead the object and record the returned version string.
24AC PowerCompare with the inverter’s live AC power.
30AC EnergyCompare the accumulated energy counter and units.
40Daily Energy YieldModel 23 only. Check the current day’s production.
42 / 43Battery power / SOCEnable Battery 1. Full battery power requires model 23.
55PowermeterEnable Powermeter and confirm an installed metering source. Model 23 only.

Check the signs before using power values

ObjectPositiveNegative
GO 42 Battery 1 powerBattery chargingBattery discharging
GO 55 PowermeterGrid importGrid export

Battery 1 Running Status (GO 41): 0 = Off, 6 = Discharging, 7 = Charging, 8 = Float charge. Compare the state with the observed operating condition.

Unavailable objects

The generic application includes objects that SMA does not supply. Objects explicitly marked Not used in Section 8 remain unavailable with either profile. Do not base automation on those objects. Model 23 only means that model 1 does not provide that value.

Interpretation and diagnostics

A zero value can be valid, such as no PV production at night or no grid exchange. Check the operating state and meter availability before treating zero as a communication fault. The Connected LED confirms inverter communication.

Manual navigation

All chapters of the INV-KNX SMA user manual

Veelgestelde vragen

Wat is het verschil tussen een groepsobject en een groepsadres?

Een groepsobject is een datapunt van het apparaat. Een groepsadres koppelt dit aan andere KNX-apparaten of visualisatie.

Wijst een meting van nul altijd op een fout?

Nee. Controleer bedrijfsomstandigheden en apparatuur voordat u nul als communicatiefout beschouwt.

Is de voeding van Battery 1 beschikbaar?

GO 42 Battery 1 power is voor deze applicatie gemarkeerd als NOT USED.

Verder verkennen