Referencia de objetos de comunicación

Referencia completa de los objetos de comunicación del INV-KNX Sungrow Hybrid, con tipos de datos y valores no disponibles.

elausys · 16 septiembre 2026
En esta página

8.1 Valores de CA y FV del sistema

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String) and GO 34-39 (Status code).

GOObject nameSizeDPT and typeMeaning and availability
1Module status1 byte20.011
DPT_ErrorClass_System
Sends 0 when the module is operating normally, sends an error code when applicable.
2Firmware version14 bytes16.000
Character string
Returns the firmware version of the device when the object is read.
3AC Current4 bytes14.019
Electric current (A)
AC Total Current value (NOT USED)
4AC Current A4 bytes14.019
Electric current (A)
AC Current phase A
5AC Current B4 bytes14.019
Electric current (A)
AC Current phase B
6AC Current C4 bytes14.019
Electric current (A)
AC Current phase C
7AC Voltage4 bytes14.027
Electric potential (V)
AC Total Voltage (NOT USED)
8AC Voltage AB4 bytes14.027
Electric potential (V)
AC Voltage phase AB
9AC Voltage BC4 bytes14.027
Electric potential (V)
AC Voltage phase BC
10AC Voltage CA4 bytes14.027
Electric potential (V)
AC Voltage phase CA
11AC Voltage AN4 bytes14.027
Electric potential (V)
AC Voltage phase AN (NOT USED)
12AC Voltage BN4 bytes14.027
Electric potential (V)
AC Voltage phase BN (NOT USED)
13AC Voltage CN4 bytes14.027
Electric potential (V)
AC Voltage phase CN (NOT USED)
14DC Current4 bytes14.019
Electric current (A)
DC Total Current value (NOT USED)
15DC Voltage4 bytes14.027
Electric potential (V)
DC Total Voltage (NOT USED)
16PV1 Voltage4 bytes14.027
Electric potential (V)
PV1 Voltage (NOT USED)
17PV1 Current4 bytes14.019
Electric current (A)
PV1 Current (NOT USED)
18PV2 Voltage4 bytes14.027
Electric potential (V)
PV2 Voltage (NOT USED)
19PV2 Current4 bytes14.019
Electric current (A)
PV2 Current (NOT USED)

8.2 Potencia, energía y diagnóstico

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String) and GO 34-39 (Status code).

GOObject nameSizeDPT and typeMeaning and availability
20PV3 Voltage4 bytes14.027
Electric potential (V)
PV3 Voltage (NOT USED)
21PV3 Current4 bytes14.019
Electric current (A)
PV3 Current (NOT USED)
22PV4 Voltage4 bytes14.027
Electric potential (V)
PV4 Voltage (NOT USED)
23PV4 Current4 bytes14.019
Electric current (A)
PV4 Current (NOT USED)
24AC Power4 bytes14.056
Power (W)
AC Power
25DC Power4 bytes14.056
Power (W)
DC Power
26AC Frequency4 bytes14.033
Frequency (Hz)
AC Frequency
27AC VA4 bytes14.056
Power (W)
AC Apparent power (NOT USED)
28AC VAR4 bytes14.056
Power (W)
AC Reactive power
29AC PF4 bytes14.057
Power factor (cos phi)
Power factor
30AC Energy4 bytes13.013
Active energy (kWh)
Total AC Energy
31Efficiency2 bytes8.010
Percentage (%)
Inverter efficiency (NOT USED)
32Insulation4 bytes14.056
Resistance (Ohm)
Insulation resistance (NOT USED)
33Temperature2 bytes9.001
Temperature (°C)
Cabinet temperature
34Status 12 bytes-
-
Device specific status code
35Status 22 bytes-
-
Device specific status code
36Status 32 bytes-
-
Device specific status code
37Status 42 bytes-
-
Device specific status code
38Status 52 bytes-
-
Device specific status code
39Status 62 bytes-
-
Device specific status code
40Daily Energy Yield4 bytes13.013
Energy (kWh)
Daily Energy Yield

8.3 Valores de batería y red

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String) and GO 34-39 (Status code).

GOObject nameSizeDPT and typeMeaning and availability
41Battery 1 Running Status2 bytes-
-
0: offline 2: standby 3: running 4: fault 5: sleep mode (NOT USED)
42Battery 1 power4 bytes14.056
Power (W)
> 0: charging < 0: discharging
43Battery 1 SOC1 byte5.001
Percentage (%)
Battery's state of capacity
44Battery 1 current day charge4 bytes13.013
Energy (kWh)
Battery 1 current day charge
45Battery 1 current day discharge4 bytes13.013
Energy (kWh)
Battery 1 current day discharge
46Battery 1 total charge4 bytes13.013
Energy (kWh)
Battery 1 total charge
47Battery 1 total discharge4 bytes13.013
Energy (kWh)
Battery 1 total discharge
48Battery 2 Running Status2 bytes-
-
0: offline 2: standby 3: running 4: fault 5: sleep mode (NOT USED)
49Battery 2 power4 bytes14.056
Power (W)
> 0: charging < 0: discharging (NOT USED)
50Battery 2 SOC1 byte5.001
Percentage (%)
Battery's state of capacity (NOT USED)
51Battery 2 current day charge4 bytes13.013
Energy (kWh)
(NOT USED)
52Battery 2 current day discharge4 bytes13.013
Energy (kWh)
(NOT USED)
53Battery 2 total charge4 bytes13.013
Energy (kWh)
(NOT USED)
54Battery 2 total discharge4 bytes13.013
Energy (kWh)
(NOT USED)
55Powermeter4 bytes14.056
Power (W)
> 0: charging < 0: discharging (NOT USED)

Active los parámetros de los equipos correspondientes en ETS. Un guion en la columna DPT indica que no se especifica ningún tipo de datos estándar. Las entradas NOT USED siguen sin estar disponibles.

Todos los capítulos del manual de usuario INV-KNX Sungrow Hybrid

Preguntas frecuentes

¿Se pueden escribir estos objetos de medición desde KNX?

Los objetos indicados usan los indicadores C R - T -: Comunicación, Lectura y Transmisión activadas; Escritura y Actualización desactivadas.

¿Qué significa NOT USED en la referencia de objetos?

La medición no está disponible para esta aplicación. Que aparezca en la aplicación ETS genérica no significa que el inversor la proporcione.

¿Qué significa un guion en la columna del tipo de datos?

Para esa entrada no se especifica ningún Type ID o Type Name estándar en esta referencia de aplicación. Use el tamaño y el significado documentado del objeto junto con la aplicación ETS.

Seguir explorando

Encuentre las demás guías de este producto en la documentación.

Volver a Manual de usuario INV-KNX Sungrow Hybrid