Problemas y errores comunes

Resuelva actualizaciones de detectores ausentes, fallos de control, tiempos de espera y escrituras de bobinas no válidas.

elausys · 17 septiembre 2026
En esta página

Not understanding zone reporting behaviour

AJAX sensors only report zone status through Modbus TCP when the system is armed or in night mode. Setting devices to Always Active enables daytime reporting, but also means those zones will trigger the alarm when the system is disarmed. Plan which zones genuinely need 24/7 Modbus TCP reporting.

Not inviting Elausys as Security Company

Area control (arm/disarm from Modbus TCP) will not work without inviting Elausys as a Security Company in the AJAX app. Internet access is also required for arming/disarming commands.

Incorrect area count with AJAX groups

Match Partition Mode and the number of areas on the gateway web interface to the AJAX group configuration. Check these settings if individual group commands behave incorrectly.

Expecting disarm to exit Night Mode

Disarming a group does not disable Night Mode when groups are enabled. You must explicitly send a Partial Arm (OFF) command to disable Night Mode. Design your controller logic to handle this independently.

Ethernet connection loss

If the Ethernet connection between the gateway and the AJAX Hub drops, the Connected LED will turn off. Detector status coils will hold their last known state until communication is restored.

Modbus TCP connection timeout

The gateway automatically closes idle Modbus TCP connections after 60 seconds of inactivity. Ensure your Modbus master is configured with a polling interval shorter than 60 seconds to maintain the connection.

Writing to read-only coils

Attempting to write to status coils (addresses 0x000B and above) will return a Modbus exception code 0x02 (Illegal Data Address). Only command coils (0x0000–0x000A) accept write operations.

Preguntas frecuentes

¿Un estado de detector mostrado demuestra que la comunicación funciona?

No. Los estados conservan su último valor conocido tras una pérdida de comunicación. Compruebe la LED Connected y la ruta de comunicación antes de confiar en el valor mostrado.

¿Always Active solo cambia la información del estado?

No. También permite que el detector active una alarma cuando el sistema está desarmado. Use esta opción solo cuando ese comportamiento sea intencionado.