Passerelles KNX pour onduleurs / Manuel d'utilisation INV-KNX SolarEdge

Référence des objets de communication

Référence complète des objets de communication de l’INV-KNX SolarEdge, avec types de données et valeurs indisponibles.

elausys · 16 septembre 2026
Sur cette page

8.1 Valeurs AC et PV du système

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String).

GOObject nameSizeDPT and typeMeaning and availability
1Module status1 byte20.011
DPT_ErrorClass_System
Sends 0 when the module is operating normally, sends an error code when applicable.
2Firmware version14 bytes16.000
Character string
Returns the firmware version of the device when the object is read.
3AC Current4 bytes14.019
Electric current (A)
AC Total Current value
4AC Current A4 bytes14.019
Electric current (A)
AC Current phase A
5AC Current B4 bytes14.019
Electric current (A)
AC Current phase B
6AC Current C4 bytes14.019
Electric current (A)
AC Current phase C
7AC Voltage4 bytes14.027
Electric potential (V)
AC Total Voltage
8AC Voltage AB4 bytes14.027
Electric potential (V)
AC Voltage phase AB
9AC Voltage BC4 bytes14.027
Electric potential (V)
AC Voltage phase BC
10AC Voltage CA4 bytes14.027
Electric potential (V)
AC Voltage phase CA
11AC Voltage AN4 bytes14.027
Electric potential (V)
AC Voltage phase AN
12AC Voltage BN4 bytes14.027
Electric potential (V)
AC Voltage phase BN
13AC Voltage CN4 bytes14.027
Electric potential (V)
AC Voltage phase CN
14DC Current4 bytes14.019
Electric current (A)
DC Total Current value
15DC Voltage4 bytes14.027
Electric potential (V)
DC Total Voltage
16PV1 Voltage4 bytes14.027
Electric potential (V)
PV1 Voltage (NOT USED)
17PV1 Current4 bytes14.019
Electric current (A)
PV1 Current (NOT USED)
18PV2 Voltage4 bytes14.027
Electric potential (V)
PV2 Voltage (NOT USED)
19PV2 Current4 bytes14.019
Electric current (A)
PV2 Current (NOT USED)

8.2 Puissance, énergie et diagnostic

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String).

GOObject nameSizeDPT and typeMeaning and availability
20PV3 Voltage4 bytes14.027
Electric potential (V)
PV3 Voltage (NOT USED)
21PV3 Current4 bytes14.019
Electric current (A)
PV3 Current (NOT USED)
22PV4 Voltage4 bytes14.027
Electric potential (V)
PV4 Voltage (NOT USED)
23PV4 Current4 bytes14.019
Electric current (A)
PV4 Current (NOT USED)
24AC Power4 bytes14.056
Power (W)
AC Power
25DC Power4 bytes14.056
Power (W)
DC Power
26AC Frequency4 bytes14.033
Frequency (Hz)
AC Frequency
27AC VA4 bytes14.056
Power (W)
AC Apparent power
28AC VAR4 bytes14.056
Power (W)
AC Reactive power
29AC PF4 bytes14.057
Power factor (cos phi)
Power factor
30AC Energy4 bytes13.013
Active energy (kWh)
Total AC Energy
31Efficiency2 bytes8.010
Percentage (%)
Inverter efficiency (NOT USED)
32Insulation4 bytes14.056
Resistance (Ohm)
Insulation resistance (NOT USED)
33Temperature2 bytes9.001
Temperature (°C)
Cabinet temperature
40Daily Energy Yield4 bytes13.013
Energy (kWh)
(NOT USED)

8.3 Valeurs de batterie et du réseau

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String).

GOObject nameSizeDPT and typeMeaning and availability
41Battery 1 Running Status2 bytes-
-
(NOT USED)
42Battery 1 power4 bytes14.056
Power (W)
> 0: charging < 0: discharging
43Battery 1 SOC1 byte5.001
Percentage (%)
Battery's state of capacity
44Battery 1 current day charge4 bytes13.013
Energy (kWh)
(NOT USED)
45Battery 1 current day discharge4 bytes13.013
Energy (kWh)
(NOT USED)
46Battery 1 total charge4 bytes13.013
Energy (kWh)
(NOT USED)
47Battery 1 total discharge4 bytes13.013
Energy (kWh)
(NOT USED)
48Battery 2 Running Status2 bytes-
-
(NOT USED)
49Battery 2 power4 bytes14.056
Power (W)
(NOT USED)
50Battery 2 SOC1 byte5.001
Percentage (%)
(NOT USED)
51Battery 2 current day charge4 bytes13.013
Energy (kWh)
(NOT USED)
52Battery 2 current day discharge4 bytes13.013
Energy (kWh)
(NOT USED)
53Battery 2 total charge4 bytes13.013
Energy (kWh)
(NOT USED)
54Battery 2 total discharge4 bytes13.013
Energy (kWh)
(NOT USED)
55Powermeter4 bytes14.056
Power (W)
> 0: charging < 0: discharging

Activez les paramètres correspondants des équipements dans ETS. Un tiret dans la colonne DPT indique qu’aucun type de données standard n’est spécifié. Les entrées NOT USED restent indisponibles.

All chapters of the INV-KNX SolarEdge user manual

Questions fréquentes

Ces objets de mesure peuvent-ils être écrits depuis KNX ?

Les objets listés utilisent les indicateurs C R - T - : Communication, Lecture et Transmission activées ; Écriture et Mise à jour désactivées.

Que signifie NOT USED dans la référence des objets ?

La mesure n’est pas disponible pour cette application. Sa présence dans l’application ETS générique ne signifie pas que l’onduleur la fournit.

Que signifie un tiret dans la colonne du type de données ?

Aucun Type ID ou Type Name standard n’est spécifié pour cette entrée. Utilisez la taille de l’objet et sa signification documentée avec l’application ETS.