Passerelles KNX pour onduleurs / Manuel d'utilisation INV-KNX SolarEdge

Référence des objets de communication

Consultez les objets de communication INV-KNX SolarEdge : numéros, tailles, datatypes KNX, drapeaux, mesures et limites.

elausys · 12 septembre 2026
Sur cette page

Gateway web configuration

The factory gateway IP address is 192.168.1.51. Connect a laptop that can reach this address and open it in a browser. Assign a free fixed IP address suitable for the installation and reconnect at the new address after applying the change.

SettingValue
ModeConnect
Server IPIP address of the inverter
Server Portthe configured inverter port (LCD default 502; SetApp default 1502)
Unit ID1; check whether the installation uses 2

The gateway Server Port must match the port actually configured on the inverter. Check the inverter Unit ID: installations with additional Modbus devices may use ID 2.

Connection check

After setting the application model and communication parameters, check that the Connected LED is on. The Network LED confirms only the physical Ethernet link; it does not confirm valid inverter data on KNX.

Configure SolarEdge

MODBUS over TCP Support

MODBUS TCP function– is disabled by default. When enabled, it supports TCP port 502 by default. Port number can be reconfigured.

SolarEdge Device Configuration – Using the Inverter/Commercial Gateway Display (LCD)

To setup MODBUS TCP:

  • Select Communication -> LAN Conf -> Modbus TCP (the default port is 502).
  • To modify the TCP port, select Modbus TCP -> TCP Port, set the port number and long-press Enter.

SolarEdge Device Configuration – Using SetApp

To setup MODBUS TCP:

  • 1 Select Communication -> Modbus TCP -> Enable. A new Port menu is added to the screen (the default port is 1502)
  • 2 To modify the TCP port, select Port, set the port number and tap Done.

The default device ID of the inverter connected to the Ethernet is 1.

The TCP server idle time is 2 minutes. In order to leave the connection open, the request should be made within 2 minutes. The connection can remain open without any MODBUS requests.

Tous les chapitres du manuel utilisateur INV-KNX SolarEdge

Questions fréquentes

Ces objets de mesure peuvent-ils être écrits depuis KNX ?

Les objets listés utilisent les drapeaux C R - T - : Communication, Lecture et Transmission activées ; Écriture et Mise à jour désactivées.

Que signifie NOT USED dans la référence des objets ?

La mesure n'est pas disponible pour cette application. Sa présence dans l'application ETS générique ne signifie pas que l'onduleur la fournit.

Que signifie un tiret dans la colonne datatype ?

Aucun Type ID ou Type Name standard n'est spécifié pour cette entrée. Utilisez la taille de l'objet et sa signification documentée avec l'application ETS.

Continuer l'exploration

Retrouvez les autres guides de ce produit dans la documentation.

Retour à Manuel d'utilisation INV-KNX SolarEdge