Naar de inhoud
Elausys

KNX Gateways voor Omvormers / INV-KNX SolarEdge Gebruikershandleiding

ETS-inbedrijfstelling

Fysieke adressering, applicatie-instellingen, koppelingen van groepsadressen en ETS-downloads voor INV-KNX SolarEdge.

elausys · 13 september 2026
Op deze pagina

Fysiek adres toewijzen

Add the appropriate Elausys INV-KNX application to the ETS project. Choose an unused physical address in the project topology; Press the gateway P button to enter programming mode and download the physical address.

Applicatieparameters instellen

Once a KNX physical address is set, open the parameter tab to configure the interface.

Select the type of AC network (single phase or tri-phase).

Set the inverter model to 2 for SolarEdge inverters.

Choose the refresh rate (min) for the complete set of data.

Select if a powermeter is available on the inverter.

Device options should remain empty.

Set the timezone and daylight-saving option when using weekly calendar logic. See Section 6 for the full parameter values and limitations.

Objecten koppelen en de applicatie downloaden

A group address (GA) must be assigned to each group object (GO) needed by the application.

Open the Group Objects tab of the device and assign a GA to the objects as needed.

When GO and parameters are all configured, download the KNX Interface application to the device. The first download requires to press the programming button on the device to set the device in KNX programming mode then perform a full download.

Resultaat controleren

Use ETS Group Monitor to check module status, read the firmware version and compare live measurements with the inverter. Follow Section 7 before enabling automation.

ETS-software

The gateway is configured with ETS from the KNX Association. ETS Demo supports projects of up to five KNX modules; the gateway occupies one module.

All chapters of the INV-KNX SolarEdge user manual

Veelgestelde vragen

Wat is nodig voor de eerste ETS-download?

Wijs het fysieke adres toe met de P-knop voor de programmeermodus. Configureer de applicatieparameters en vereiste groepsadreskoppelingen en voer een volledige download uit.

Wat moet ik controleren na het downloaden van de applicatie?

Gebruik ETS Group Monitor om de module status en firmware te lezen en vergelijk live metingen na het pollinginterval met de omvormer.

Verder verkennen

Vind de andere handleidingen voor dit product in de documentatie.

Terug naar INV-KNX SolarEdge Gebruikershandleiding