KNX Gateways voor Omvormers / INV-KNX SolarEdge Gebruikershandleiding

Referentie communicatieobjecten

Bekijk de INV-KNX SolarEdge-communicatieobjecten met nummers, groottes, KNX-datatypes, vlaggen, betekenissen en beschikbaarheidslimieten.

elausys · 12 september 2026
Op deze pagina

Gateway web configuration

The factory gateway IP address is 192.168.1.51. Connect a laptop that can reach this address and open it in a browser. Assign a free fixed IP address suitable for the installation and reconnect at the new address after applying the change.

SettingValue
ModeConnect
Server IPIP address of the inverter
Server Portthe configured inverter port (LCD default 502; SetApp default 1502)
Unit ID1; check whether the installation uses 2

The gateway Server Port must match the port actually configured on the inverter. Check the inverter Unit ID: installations with additional Modbus devices may use ID 2.

Connection check

After setting the application model and communication parameters, check that the Connected LED is on. The Network LED confirms only the physical Ethernet link; it does not confirm valid inverter data on KNX.

Configure SolarEdge

MODBUS over TCP Support

MODBUS TCP function– is disabled by default. When enabled, it supports TCP port 502 by default. Port number can be reconfigured.

SolarEdge Device Configuration – Using the Inverter/Commercial Gateway Display (LCD)

To setup MODBUS TCP:

  • Select Communicatie -> LAN Conf -> Modbus TCP (the default port is 502).
  • To modify the TCP port, select Modbus TCP -> TCP Port, set the port number and long-press Enter.

SolarEdge Device Configuration – Using SetApp

To setup MODBUS TCP:

  • 1 Select Communicatie -> Modbus TCP -> Enable. A new Port menu is added to the screen (the default port is 1502)
  • 2 To modify the TCP port, select Port, set the port number and tap Done.

The default device ID of the inverter connected to the Ethernet is 1.

The TCP server idle time is 2 minutes. In order to leave the connection open, the request should be made within 2 minutes. The connection can remain open without any MODBUS requests.

Alle hoofdstukken van de INV-KNX SolarEdge-gebruikershandleiding

Veelgestelde vragen

Kunnen deze meetobjecten vanuit KNX worden beschreven?

De vermelde objecten gebruiken de vlaggen C R - T -: Communicatie, Lezen en Verzenden zijn ingeschakeld; Schrijven en Bijwerken zijn uitgeschakeld.

Wat betekent NOT USED in de objectreferentie?

De meting is niet beschikbaar voor deze toepassing. Dat ze in de generieke ETS-toepassing voorkomt, betekent niet dat de omvormer ze levert.

Wat betekent een streepje in de kolom datatype?

Voor die vermelding in deze toepassingsreferentie is geen standaard Type ID of Type Name opgegeven. Gebruik de objectgrootte en de gedocumenteerde betekenis naast de ETS-toepassing.

Verder verkennen

Vind de andere handleidingen voor dit product in de documentatie.

Terug naar INV-KNX SolarEdge Gebruikershandleiding