Atuadores KNX / Manual do Utilizador MSA-810

Controlo de válvulas e temperatura

Controlo de válvulas com ligar/desligar, limites, PWM, controlo PI e controlo de temperatura de dois pontos.

elausys · 11 setembro 2026
Nesta página

Valve control

To control valves, five operating modes are available:

PARAMETERVALUESDESCRIPTION
ControlOn/Off (default) Limit values PWM PI Temperature control 2-points Temperature controlDepending on the control mode, specific parameters are displayed.
TypeNormally closed (default) Normally openIn case of normally open valve, the output state is inverted.
Valve protectionDisabled (default) EnabledWhen enabled, the valve is automatically activated for 5 minutes every 24h as a protection for long durations without activation.
Send output statusDisabled (default) EnabledWhen enabled, the valve output status is send using a dedicated status object.

On/off control

On/Off control is used to control the valve directly using the corresponding group object. The output follows the state of the input command.

Communication Objects

NRNAMEFUNCTIONSIZEFLAGSTYPE
1BlockOn/Off1 bitCRWDPT_Enable
3Valve On/OffOn/Off1 bitCWDPT_Switch
5StateOn/Off1 bitCRTDPT_Switch

Limit values control

The valve control is performed by percentages. When this option is enabled, it is necessary to configure 2 parameters that define the hysteresis value.

PARAMETERVALUESDESCRIPTION
Upper limit (%)From 0 to 100%The upper limit determines when the valve is activated (it must be greater than 0).
Lower limit (%)From 0 to 100%The lower limit determines when the valve is deactivated (value must be smaller than the upper limit).

Communication Objects

NRNAMEFUNCTIONSIZEFLAGSTYPE
1BlockOn/Off1 bitCRWDPT_Enable
5StateOn/Off1 bitCRTDPT_Switch
7Control valuePercent1 byteCWDPT_Percent

PWM control

The PWM cycle time is used for calculating the on and off pulses of the control value. This calculation

is based on the incoming control value. A PWM cycle includes the whole time which elapses from

one switch-on pulse to the next.

PARAMETERVALUESDESCRIPTION
PWM cycle (min)From 1 to 255 min.Defines the cycle period for the PWM control.
Upper limit (%)From 0 to 100%The upper limit of the input command value. The received value will be limited by this setting.
Lower limit (%)From 0 to 100%The lower limit of the input command value. The received value will be limited by this setting.

Communication Objects

NRNAMEFUNCTIONSIZEFLAGSTYPE
1BlockOn/Off1 bitCRWDPT_Enable
5StateOn/Off1 bitCRTDPT_Switch
7Control valuePercent1 byteCWDPT_Percent

PI temperature control

The PI temperature controller allows to directly control the valve based on the room temperature. The temperature controller can be used for heating, cooling or combined heating and cooling.

PARAMETERVALUESDESCRIPTION
Scene control: Scene 1 Scene 2 Scene 3 Scene 40 (default) 1 to 64When set to 0 the channel will ignore corresponding scene. When set to another value, the channel will respond to this scene number. Channel state can be store using the scene group object for further recall.
PWM cycle (min)From 1 to 255 min.Defines the cycle period for the PWM output of the control.
Proportional band4 (default) 1 – 20Proportional band of the PI controller
Reset time120 min. (default) 15 – 240 minReset time of the PI controller
Minimum output0% (default) 0 – 100 %Minimum output of the controller
Maximum output100% (default) 0 – 100 %Maximum output of the controller
Heating/Cooling modeCooling Heating (default) Cooling/Heating group objectOperating mode of the controller. When choosing the mode from the group object, a general “Heating/Cooling switch” object is used to change the operating mode of all temperature controllers.
Comfort setpoint21°C (default) 14-25°CTemperature setpoint in comfort mode
Standby reduction for heating3°C (default) 0-10°CTemperature setpoint reduction in standby mode for heating
Night reduction for heating1.5°C (default) 0-10°CTemperature setpoint reduction in night mode for heating
Standby increase for cooling3°C (default) 0-10°CTemperature setpoint increase in standby mode for cooling
Night increase for cooling1.5°C (default) 0-10°CTemperature setpoint increase in night mode for cooling

Setting the proportional band and reset time depending on the type of installation:

  • Warm water heating: (4 / 120min)
  • Underfloor heating: (4 / 150min)
  • Split Unit: (4 / 60min)

Communication Objects

NRNAMEFUNCTIONSIZEFLAGSTYPE
1BlockOn/Off1 bitCRWDPT_Enable
2SceneScene1 byteCWDPT_Scene
3Setpoint Offset (0 = - / 1 = +)+/-1 bitCWDPT_Step
4Mode selectionMode1 byteCWDPT_HVACMode
5StateOn/Off1 bitCRTDPT_Switch
6Comfort setpointValue2 bytesCWDPT_Value_Temp
7Temperature valueValue2 bytesCWDPT_Value_Temp
8Controller output valuePercent1 byteCRTDPT_Scaling
9Mode StatusMode1 byteCRTDPT_HVACMode
10Current setpointValue2 bytesCRTDPT_Value_Temp

2-points temperature control

The 2-points temperature controller allows to directly control the valve based on the room temperature. The temperature controller can be used for heating, cooling or combined heating and cooling.

PARAMETERVALUESDESCRIPTION
Scene control: Scene 1 Scene 2 Scene 3 Scene 40 (default) 1 to 64When set to 0 the channel will ignore corresponding scene. When set to another value, the channel will respond to this scene number. Channel state can be store using the scene group object for further recall.
Switching hysteresis0.5°C (default) 0-10°CThe switching hystereris defines the switch on and off triggers for the channel output. The channel is switched on if the temperature is lower than the setpoint - hysteresis and is is switched off if the temperature is greater or equal to the setpoint.
Heating/Cooling modeCooling Heating (default) Cooling/Heating group objectOperating mode of the controller. When choosing the mode from the group object, a general “Heating/Cooling switch” object is used to change the operating mode of all temperature controllers.
Comfort setpoint21°C (default) 14-25°CTemperature setpoint in comfort mode
Standby reduction for heating3°C (default) 0-10°CTemperature setpoint reduction in standby mode for heating
Night reduction for heating1.5°C (default) 0-10°CTemperature setpoint reduction in night mode for heating
Standby increase for cooling3°C (default) 0-10°CTemperature setpoint increase in standby mode for cooling
Night increase for cooling1.5°C (default) 0-10°CTemperature setpoint increase in night mode for cooling

Communication Objects

NRNAMEFUNCTIONSIZEFLAGSTYPE
1BlockOn/Off1 bitCRWDPT_Enable
2SceneScene1 byteCWDPT_Scene
3Setpoint Offset (0 = - / 1 = +)+/-1 bitCWDPT_Step
4Mode selectionMode1 byteCWDPT_HVACMode
5StateOn/Off1 bitCRTDPT_Switch
6Comfort setpointValue2 bytesCWDPT_Value_Temp
7Temperature valueValue2 bytesCWDPT_Value_Temp
9Mode StatusMode1 byteCRTDPT_HVACMode
10Current setpointValue2 bytesCRTDPT_Value_Temp

Manual navigation

All manual articles

Perguntas frequentes

Que modos de controlo de válvulas estão disponíveis?

A referência abrange ligar/desligar, valores limite, PWM, controlo de temperatura PI e controlo de temperatura de dois pontos.

O controlador de temperatura pode gerir aquecimento e arrefecimento?

Os controladores PI e de dois pontos suportam aquecimento, arrefecimento ou ambos, de acordo com a configuração.