A tabela apresenta a alimentação externa, a tensão do bus KNX, as saídas de comutação e os limites de funcionamento.
| DESCRIPTION | VALUES |
|---|---|
| External Power supply | 24-30 VDC |
| Max. auxiliary consumption | < 0,5 A @ 30VDC |
| KNX bus voltage | 29 VDC |
| Operating temperature | 0 to + 45°C |
| Enclosure | IP20 |
| Dimensions (Space Units) | 4SU |
| KNX Terminal | Pluggable micro terminal, Red/Black, 4 pole PUSH WIRE for solid conductor wire 0.6-0.8 mm² |
| Switching outputs | 8 |
| Output rated voltage | 230 VAC |
| Rated resistive load | 10 A |
| Output life expectancy (mechanical) | 10.000.000 |
| Max. total current of the actuator | 25A |
| Screw terminal section | 2,5mm² |
| Torque screw terminal | 0,5Nm |
| Max. extension modules | 8 |
| Max. SAE-x10 extensions | Max. 40 channels 10A (Combined on MSA-810 / SAE-810 / SAE-2410) |
| Max. number of channels | 72 |
| Available application software | ETS5 / ETS6 |
Use the individual extension datasheets for their wiring diagrams and electrical ratings. Product information and support: elausys.com.