Funções da saída analógica, parâmetros ETS e objetos de comunicação KNX.
Features
- The analog output value is received as a percentage from the bus and is applied to the analog output.
- Blocking function can be set by a group object for each channel to prevent operating the channel from the bus.
- Minimum and maximum output can be adjustable.
- Output change speed adjustable.
- Up to 4 internal scenes configurable per output.
- Output status feedback.
Parameters
| PARAMETER | VALUES | DESCRIPTION |
|---|
| Scene control: Scene 1 Scene 2 Scene 3 Scene 4 | 0 (default) 1 to 64 | When set to 0 the channel will ignore corresponding scene. When set to another value, the channel will respond to this scene number. Channel state can be store using the scene group object for further recall. |
| Switch ON delay Switch OFF delay | No delay 250ms to 60 min. | The ON or OFF delay causes a delayed switch of the channel. At sending a new switch signal to the channel, first the adjusted delay time expires and afterwards the channel will be switched. |
| Minimum output | 0% (default) 0 to 100% | Adjust the minimum output percentage. In case a setpoint value lower than this value is received the output is switched off. |
| Maximum output | 100% (default) 0 to 100% | Adjust the maximum output percentage. |
| Output change duration | 1s (default) 0 to 60s | Duration to go from 0 to 100%. |
| Send output status value | Enabled (default) Disabled | When enabled the output value is sent to a status group object. |
Communication Objects
| NR | NAME | FUNCTION | SIZE | FLAGS | TYPE |
|---|
| 1 | Block | On/Off | 1 bit | CRW | DPT_Enable |
| 2 | Scene | Scene | 1 byte | CW | DPT_SceneControl |
| 7 | Analog Control value | Percent | 1 byte | CW | DPT_Scaling |
| 8 | Analog Output value | Percent | 1 byte | CRT | DPT_Scaling |