Configuração de rede e Modbus

Definições de rede da gateway e configuração SMA necessária para estabelecer a comunicação Modbus.

elausys · 12 setembro 2026
Nesta página

Gateway web configuration

The factory gateway IP address is 192.168.1.51. Connect a laptop that can reach this address and open it in a web browser. If the page is unreachable, check the Ethernet link, the laptop network settings and whether the gateway already has a different IP address.

Assign the gateway a free fixed IP address suitable for the installation. Record it and reconnect at the new address after applying the network change.

SettingValue
ModeConnect
IP / server addressIP address of the SMA inverter
Server Port502, or the matching TCP port configured on the inverter
Unit Id3 with model 23; 126 with model 1

Always connect to the inverter IP address. Do not use the Sunny Home Manager IP address. A Sunny Home Manager is not required for model 23. Grid power comes from the inverter’s grid-metering registers, which depend on an installed SMA Energy Meter or Sunny Home Manager. Without this metering source, grid power may be zero or unavailable.

Enable the SMA TCP server in Sunny Explorer

Use this procedure on inverters configured through Sunny Explorer. Create a Speedwire system as described in the Sunny Explorer user manual. For a different inverter interface, use the corresponding SMA instructions to enable the same Modbus TCP server settings.

  1. Start Sunny Explorer and open or create the Speedwire system.
  2. Log into the system as Installer.
  3. Select the SMA inverter in the system tree.
  4. Open Settings, then External Communication.
  5. Select Edit. Under Modbus, locate TCP Server.
  6. Set Modbus > TCP Server > Activated to Yes.
  7. Keep port 502, or set a different port and enter the same port in the gateway.
  8. Select Save.

Connection check

After configuring the model and Unit Id, check that the Connected LED is on. A Network LED alone confirms only the physical Ethernet link. It does not confirm Modbus communication or valid KNX data.

Manual navigation

All chapters of the INV-KNX SMA user manual

Perguntas frequentes

Qual é o endereço IP de fábrica da gateway?

O endereço de fábrica é 192.168.1.51. Use um computador portátil que consiga aceder-lhe, atribua um endereço IP fixo livre e ligue-se novamente no novo endereço.

Que definições de ligação Modbus devo utilizar?

Use o modo Connect e o endereço IP do inversor. Defina a porta 502 ou a porta TCP configurada no inversor. Use Unit Id 3 com o modelo 23 ou 126 com o modelo 1. Não direcione para o Sunny Home Manager.