Saltar para o conteúdo
Elausys

Portas KNX para Inversores / Manual do Utilizador INV-KNX SMA

Referência dos parâmetros ETS

Tabela completa de parâmetros ETS e orientações específicas da aplicação para o INV-KNX SMA.

elausys · 14 setembro 2026
Nesta página

These parameters are in the device Parameters tab. The generic INV-KNX application exposes options for several inverter families; the SMA limits below take precedence.

ParameterValuesSMA configuration guidance
AC NetworkSingle phase (default) / Tri-PhaseSelect the installed AC network.
Number of PV Circuits1-4 in the generic applicationUse 1 or 2 for this SMA application. PV3 and PV4 objects are not used.
Inverter model0-25523 = SMA Sunny Tripower Smart Energy, SMA native profile, Unit Id 3 (default). 1 = SMA SBX0, SunSpec profile, Unit Id 126 (legacy).
Refresh rate (min)0-255Cyclic interval for polling the complete inverter data set.
Battery 1Not Used / UsedEnable for the installed battery. Full battery power and lifetime energy data require model 23. For model 23, battery objects are read only when this option is enabled.
Battery 2Not Used / UsedNot used for this SMA application. Leave Not Used.
PowermeterNot Used / UsedModel 23 only. Enable when the installation supplies energy-meter data to the inverter. The object is read only when enabled.
TimezoneUTC-11 to UTC+14Installation timezone for logic functions using the weekly calendar.
Daylight saving timeNot Used / Used (default)Select whether daylight saving applies to weekly calendar logic at the site.
Device OptionsText stringNot available on this device. Leave empty.

Model dependent data

Select model 23 for installations requiring battery power, total charged or discharged battery energy, or the power meter object. Model 1 does not provide those values. An enabled object is useful only if the connected inverter and installed equipment provide its measurement.

Refresh rate

Allow at least the configured polling interval before judging whether values are updating. A slow interval can look like stale data during commissioning. Select the interval required by the project and verify its effect in ETS Group Monitor.

Manual navigation

All chapters of the INV-KNX SMA user manual

Perguntas frequentes

Que modelo de inversor devo selecionar?

Use o modelo 23 com Unit Id 3 da gateway para novas instalações. A opção SunSpec antiga usa o modelo 1 com Unit Id 126; o ID do inversor é 3.

O que devo introduzir em Device Options?

Deixe Device Options vazio.

A ativação de um objeto opcional garante uma medição?

Não. O modelo de inversor selecionado e o equipamento instalado devem fornecer essa medição. Consulte a tabela de disponibilidade.

Continuar a explorar

Encontre os outros guias deste produto na documentação.

Voltar a Manual do Utilizador INV-KNX SMA