Skip to content
Elausys

KNX Gateways for Inverters / INV-KNX Huawei User Manual

Communication object reference

The full communication-object reference for INV-KNX Huawei, including datatypes and unavailable values.

elausys · 16 September 2026
On this page

8.1 System AC and PV values

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String) and GO 34-39 (Status code).

GOObject nameSizeDPT and typeMeaning and availability
1Module status1 byte20.011
DPT_ErrorClass_System
Sends 0 when the module is operating normally, sends an error code when applicable.
2Firmware version14 bytes16.000
Character string
Returns the firmware version of the device when the object is read.
3AC Current4 bytes14.019
Electric current (A)
AC Total Current value
4AC Current A4 bytes14.019
Electric current (A)
AC Current phase A
5AC Current B4 bytes14.019
Electric current (A)
AC Current phase B
6AC Current C4 bytes14.019
Electric current (A)
AC Current phase C
7AC Voltage4 bytes14.027
Electric potential (V)
AC Total Voltage
8AC Voltage AB4 bytes14.027
Electric potential (V)
AC Voltage phase AB
9AC Voltage BC4 bytes14.027
Electric potential (V)
AC Voltage phase BC
10AC Voltage CA4 bytes14.027
Electric potential (V)
AC Voltage phase CA
11AC Voltage AN4 bytes14.027
Electric potential (V)
AC Voltage phase AN
12AC Voltage BN4 bytes14.027
Electric potential (V)
AC Voltage phase BN
13AC Voltage CN4 bytes14.027
Electric potential (V)
AC Voltage phase CN
14DC Current4 bytes14.019
Electric current (A)
DC Total Current value (NOT USED)
15DC Voltage4 bytes14.027
Electric potential (V)
DC Total Voltage (NOT USED)
16PV1 Voltage4 bytes14.027
Electric potential (V)
PV1 Voltage
17PV1 Current4 bytes14.019
Electric current (A)
PV1 Current
18PV2 Voltage4 bytes14.027
Electric potential (V)
PV2 Voltage
19PV2 Current4 bytes14.019
Electric current (A)
PV2 Current

8.2 Power energy and diagnostics

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String) and GO 34-39 (Status code).

GOObject nameSizeDPT and typeMeaning and availability
20PV3 Voltage4 bytes14.027
Electric potential (V)
PV3 Voltage
21PV3 Current4 bytes14.019
Electric current (A)
PV3 Current
22PV4 Voltage4 bytes14.027
Electric potential (V)
PV4 Voltage
23PV4 Current4 bytes14.019
Electric current (A)
PV4 Current
24AC Power4 bytes14.056
Power (W)
AC Power
25DC Power4 bytes14.056
Power (W)
DC Power
26AC Frequency4 bytes14.033
Frequency (Hz)
AC Frequency
27AC VA4 bytes14.056
Power (W)
AC Apparent power (NOT USED)
28AC VAR4 bytes14.056
Power (W)
AC Reactive power (NOT USED)
29AC PF4 bytes14.057
Power factor (cos phi)
Power factor
30AC Energy4 bytes13.013
Active energy (kWh)
Total AC Energy
31Efficiency2 bytes8.010
Percentage (%)
Inverter efficiency
32Insulation4 bytes14.056
Resistance (Ohm)
Insulation resistance
33Temperature2 bytes9.001
Temperature (°C)
Cabinet temperature
34Status 12 bytes-
-
Device specific status code
35Status 22 bytes-
-
Device specific status code
36Status 32 bytes-
-
Device specific status code
37Status 42 bytes-
-
Device specific status code
38Status 52 bytes-
-
Device specific status code
39Status 62 bytes-
-
Device specific status code
40Daily Energy Yield4 bytes13.013
Energy (kWh)
Daily Energy Yield

8.3 Battery and grid values

All listed objects use flags C R - T -: Communication, Read and Transmit enabled; Write and Update disabled. Function: Actual value, except GO 1 (Status code), GO 2 (Text String) and GO 34-39 (Status code).

GOObject nameSizeDPT and typeMeaning and availability
41Battery 1 Running Status2 bytes-
-
0: offline 2: standby 3: running 4: fault 5: sleep mode
42Battery 1 power4 bytes14.056
Power (W)
> 0: charging < 0: discharging
43Battery 1 SOC1 byte5.001
Percentage (%)
Battery's state of capacity
44Battery 1 current day charge4 bytes13.013
Energy (kWh)
Battery 1 current day charge
45Battery 1 current day discharge4 bytes13.013
Energy (kWh)
Battery 1 current day discharge
46Battery 1 total charge4 bytes13.013
Energy (kWh)
Battery 1 total charge
47Battery 1 total discharge4 bytes13.013
Energy (kWh)
Battery 1 total discharge
48Battery 2 Running Status2 bytes-
-
0: offline 2: standby 3: running 4: fault 5: sleep mode
49Battery 2 power4 bytes14.056
Power (W)
> 0: charging < 0: discharging
50Battery 2 SOC1 byte5.001
Percentage (%)
Battery's state of capacity
51Battery 2 current day charge4 bytes13.013
Energy (kWh)
Battery 2 current day charge
52Battery 2 current day discharge4 bytes13.013
Energy (kWh)
Battery 2 current day discharge
53Battery 2 total charge4 bytes13.013
Energy (kWh)
Battery 2 total charge
54Battery 2 total discharge4 bytes13.013
Energy (kWh)
Battery 2 total discharge
55Powermeter4 bytes14.056
Power (W)
> 0: charging < 0: discharging

Enable the corresponding equipment parameters in ETS. A dash in the DPT column indicates that no standard datatype is specified. NOT USED entries remain unavailable.

EMMA communication objects

8.4 EMMA availability and meaning

For model 21, the following inverter measurements are listed for EMMA. GO 27 remains NOT USED. Sizes, datatypes and flags are given in Sections 8.1-8.3; GO 1 and GO 2 are the general device objects.

GOObject nameEMMA meaning and availability
4AC Current AAC Current phase A
5AC Current BAC Current phase B
6AC Current CAC Current phase C
8AC Voltage ABAC Voltage phase AB
9AC Voltage BCAC Voltage phase BC
10AC Voltage CAAC Voltage phase CA
11AC Voltage ANAC Voltage phase AN
12AC Voltage BNAC Voltage phase BN
13AC Voltage CNAC Voltage phase CN
24AC PowerAC Power
25DC PowerDC Power
27AC VAAC Apparent power (NOT USED)
29AC PFPower factor
30AC EnergyTotal AC Energy
40Daily Energy Yield
42Battery 1 power> 0: charging < 0: discharging
43Battery 1 SOCBattery's state of capacity
44Battery 1 current day charge
45Battery 1 current day discharge
46Battery 1 total charge
47Battery 1 total discharge
55Powermeter< 0: charging > 0: discharging

Manual navigation

All chapters of the INV-KNX Huawei user manual

Frequently Asked Questions

Can these measurement objects be written from KNX?

The listed objects use flags C R - T -: Communication, Read and Transmit are enabled; Write and Update are disabled.

What does NOT USED mean in the object reference?

The measurement is unavailable for this application. Its presence in the generic ETS application does not mean the inverter supplies it.

What does a dash in the datatype column mean?

No standard Type ID or Type Name is specified for that entry in this application reference. Use the object size and documented meaning alongside the ETS application.

Keep exploring

Find the other guides for this product in the documentation.

Back to INV-KNX Huawei User Manual