Network and inverter configuration

Gateway network settings and the Kostal configuration needed to establish Modbus communication.

elausys · 12 September 2026
On this page

Gateway web configuration

The factory gateway IP address is 192.168.1.51. Connect a laptop that can reach this address and open it in a browser. Assign a free fixed IP address suitable for the installation and reconnect at the new address after applying the change.

SettingValue
ModeConnect
Server IPIP address of the inverter
Server Port1502
Unit ID71

Connection check

After setting the application model and communication parameters, check that the Connected LED is on. The Network LED confirms only the physical Ethernet link; it does not confirm valid inverter data on KNX.

Configure Kostal

Refer to the inverter manual to enable MODBUS over TCP Support

To setup MODBUS TCP:

  • Check that the Modbus TCP is enabled
  • Check the port number (default : 1502)
  • Check the inverter U-ID (default : 71)

Manual navigation

All chapters of the INV-KNX Kostal user manual

Frequently Asked Questions

What is the gateway factory IP address?

The factory address is 192.168.1.51. Use a laptop that can reach this address, assign a suitable free fixed IP address and reconnect at the new address.

Which Modbus connection settings should I use?

Use Connect mode and the inverter IP address. The documented default Modbus TCP port is 1502 and Unit ID is 71; verify the inverter settings.