Network and inverter configuration

Gateway network settings and the Sungrow Hybrid configuration needed to establish Modbus communication.

elausys · 12 September 2026
On this page

Gateway web configuration

The factory gateway IP address is 192.168.1.51. Connect a laptop that can reach this address and open it in a browser. Assign a free fixed IP address suitable for the installation and reconnect at the new address after applying the change.

SettingValue
ModeConnect
Server IPIP address of the inverter
Server Port502
Unit ID1

Connection check

After setting the application model and communication parameters, check that the Connected LED is on. The Network LED confirms only the physical Ethernet link; it does not confirm valid inverter data on KNX.

Configure Sungrow Hybrid

Modbus TCP must be enabled on the inverter, refer to the inverter user manual.

Manual navigation

All chapters of the INV-KNX Sungrow Hybrid user manual

Frequently Asked Questions

What is the gateway factory IP address?

The factory address is 192.168.1.51. Use a laptop that can reach this address, assign a suitable free fixed IP address and reconnect at the new address.

Which Modbus connection settings should I use?

Use Connect mode, the inverter IP address, port 502 and Unit ID 1. Enable Modbus TCP using the inverter instructions.