ETS commissioning

Physical addressing, application settings, group-address links and ETS downloads for INV-KNX Sigenergy.

elausys · 13 September 2026
On this page

Assign the physical address

Add the appropriate Elausys INV-KNX application to the ETS project. Choose an unused physical address in the project topology; Press the gateway P button to enter programming mode and download the physical address.

Set the application parameters

Once a KNX physical address is set, open the Parameters tab to configure the interface.

  • Select the type of AC network (single phase or tri-phase).
  • Select the number of solar panel circuits to monitor.
  • Set the inverter model to 20 for the Sigenergy SigenStor.
  • Choose the refresh rate (min) for the complete set of data.
  • Select if batteries or a powermeter are available on the inverter.
  • Device options should remain empty.

Set the timezone and daylight-saving option when using weekly calendar logic. See Section 6 for the full parameter values and limitations.

A group address (GA) must be assigned to each group object (GO) needed by the application. Open the Group Objects tab of the device and assign a GA to the objects as needed.

When the group objects and parameters are all configured, download the KNX interface application to the device. The first download requires pressing the programming button on the device to set it in KNX programming mode, then performing a full download.

Verify the result

Use ETS Group Monitor to check module status, read the firmware version and compare live measurements with the inverter. Follow Section 7 before enabling automation.

ETS software

The gateway is configured with ETS from the KNX Association. ETS Demo supports projects of up to five KNX modules; the gateway occupies one module.

Manual navigation

All chapters of the INV-KNX Sigenergy user manual

Frequently Asked Questions

What is required for the first ETS download?

Assign the physical address using the P button for programming mode. Configure the application parameters and required group-address links, then perform a full download.

What should I check after downloading the application?

Use ETS Group Monitor to read module status and firmware, then compare live measurements with the inverter after the polling interval.