General objects
| GO | Object | Function |
|---|---|---|
| 1 | Module status | Sends 0 during normal operation or an error code when applicable. |
| 2 | Firmware | Device firmware version as a text string; also sent at startup. |
| 233 | Call scene | Sends the configured scene number when an area status becomes active. |
Object groups
Each zone has one status object. Each area has 12 objects: three commands and nine statuses. The area 1 functions repeat for areas 2 to 4. The tables identify the objects and the repeated groups.
| GO | Object | Meaning |
|---|---|---|
| 163 | AC Failure | Active when the alarm system main power supply is down. |
| 164 | Battery Failure | Active when the battery is low. |
Reading the reference tables
Each row lists the function, size, flags, Type ID, Type Name, range and description. Flags are ordered C R W T U: Communication, Read, Write, Transmit and Update. A dash means that flag is not set. Entries marked NOT USED are unavailable for this application.
Repeated ranges use the same metadata as the adjacent representative rows. Do not assign unavailable functions merely because the generic ETS application exposes them. Exact active objects are selected by the parameters in ETS parameter reference.
PG and zone objects
| GO | Object name | Size | DPT and type | Meaning and access |
|---|---|---|---|---|
| 1 | Module status | 1 byte | 20.011 DPT_ErrorClass_System | Device error code Function: Status code Flags: C R - T - |
| 2 | Firmware | 14 bytes | 16.000 DPT_String_ASCII | Device firmware version Function: Text string Flags: C R - T - |
| 3 | PG1 | 1 bit | 1.001 DPT_Switch | PG – On/Off (NOT USED) Function: On/Off Flags: C - W - - Range: 0..1 |
| 4 | PG1 Status | 1 bit | 1.001 DPT_Switch | PG – On/Off status (NOT USED) Function: On/Off Flags: C R - T - Range: 0..1 |
| 5 | PG2 | 1 bit | 1.001 DPT_Switch | PG – On/Off (NOT USED) Function: On/Off Flags: C - W - - Range: 0..1 |
| 6 | PG2 Status | 1 bit | 1.001 DPT_Switch | PG – On/Off status (NOT USED) Function: On/Off Flags: C R - T - Range: 0..1 |
| … | Same for PG3 to PG31 | |||
| 64 | PG32 | 1 bit | 1.001 DPT_Switch | PG – On/Off (NOT USED) Function: On/Off Flags: C - W - - Range: 0..1 |
| 66 | PG32 Status | 1 bit | 1.001 DPT_Switch | PG – On/Off status (NOT USED) Function: On/Off Flags: C R - T - Range: 0..1 |
| 67 | Zone 1 Status | 1 bit | 1.001 DPT_Switch | Zone – On/Off status Function: On/Off Flags: C R - T - Range: 0..1 |
| 68 | Zone 2 Status | 1 bit | 1.001 DPT_Switch | Zone – On/Off status Function: On/Off Flags: C R - T - Range: 0..1 |
| … | Same for Zone 3 to 95 | |||
| 162 | Zone 96 Status | 1 bit | 1.001 DPT_Switch | Zone – On/Off status Function: On/Off Flags: C R - T - Range: 0..1 |
Supply and virtual input objects
| GO | Object name | Size | DPT and type | Meaning and access |
|---|---|---|---|---|
| 163 | AC Failure | 1 bit | 1.001 DPT_Switch | On/Off status Function: On/Off Flags: C R - T - Range: 0..1 |
| 164 | Battery Failure | 1 bit | 1.001 DPT_Switch | On/Off status Function: On/Off Flags: C R - T - Range: 0..1 |
| 169 | Virtual input 1 | 1 bit | 1.001 DPT_Switch | Open/close input (NOT USED) Function: Open/Close Flags: C - W - - Range: 0..1 |
| 170 | Virtual input 2 | 1 bit | 1.001 DPT_Switch | Open/close input (NOT USED) Function: Open/Close Flags: C - W - - Range: 0..1 |
| … | Same for input 3 to 15 | |||
| 184 | Virtual input 16 | 1 bit | 1.001 DPT_Switch | Open/close input (NOT USED) Function: Open/Close Flags: C - W - - Range: 0..1 |
Area commands status and scenes
| GO | Object name | Size | DPT and type | Meaning and access |
|---|---|---|---|---|
| 185 | Area 1 - Arm | 1 bit | 1.017 DPT_Switch | Arm Area Function: On/Off Flags: C - W - - Range: 0..1 |
| 186 | Area 1 – Partial arm | 1 bit | 1.017 DPT_Switch | Partial arm Area Function: On/Off Flags: C - W - - Range: 0..1 |
| 187 | Area 1 – Disarm | 1 bit | 1.017 DPT_Trigger | Disarm Area Function: On Flags: C - W - - Range: 0..1 |
| 188 | Area 1 – state disarmed | 1 bit | 1.001 DPT_Switch | Area state disarmed Function: On/Off Flags: C R - T - Range: 0..1 |
| 189 | Area 1 – entry delay | 1 bit | 1.001 DPT_Switch | Area entry delay status Function: On/Off Flags: C R - T - Range: 0..1 |
| 190 | Area 1 – exit delay | 1 bit | 1.001 DPT_Switch | Area exit delay status Function: On/Off Flags: C R - T - Range: 0..1 |
| 191 | Area 1 – state armed | 1 bit | 1.001 DPT_Switch | Area state armed status Function: On/Off Flags: C R - T - Range: 0..1 |
| 192 | Area 1 – state partial armed | 1 bit | 1.001 DPT_Switch | Area state partial armed status Function: On/Off Flags: C R - T - Range: 0..1 |
| 193 | Area 1 – Fire alarm | 1 bit | 1.001 DPT_Switch | Area fire alarm Function: On/Off Flags: C R - T - Range: 0..1 |
| 194 | Area 1 – Siren ON | 1 bit | 1.001 DPT_Switch | Area siren ON Function: On/Off Flags: C R - T - Range: 0..1 |
| 195 | Area 1 – Panic alarm | 1 bit | 1.001 DPT_Switch | Area panic alarm Function: On/Off Flags: C R - T - Range: 0..1 |
| 196 | Area 1 – Intrusion alarm | 1 bit | 1.001 DPT_Switch | Area intrusion alarm Function: On/Off Flags: C R - T - Range: 0..1 |
| … | Same for AREA 2 to 4 | |||
| 233 | Call scene | 1 Byte | 18.001 DPT_SceneControl | Scene control Function: - Flags: C - - T - Range: 1..64 |