Group addresses and validation

Practical checks for group addresses, alarm data, commands and KNX scene recalls.

elausys · 16 September 2026
On this page

A group object (GO) is a datapoint in the gateway. A group address (GA) links it to other KNX devices or a visualisation. Match each group address to the size and datatype in Communication object reference.

CheckExpected result
Module status (GO 1)0 when operating normally; a non-zero code indicates an error.
Firmware (GO 2)A version string is returned. Check the firmware applicability in Firmware and technical data.
Zone statusOpen and close an enabled zone and compare the KNX value with the alarm system. Account for the configured zone offset.
Area statusConfirm that status changes follow the mapped area and the Send area status setting.
Area controlCheck arm, partial arm and disarm for the mapped area using the configured user code. See the ON/OFF behaviour in ETS parameter reference.
Scenes (GO 233)An active area status sends the configured scene number. Scene 0 disables the recall.

Confirm the Network and Connected LEDs. Check enabled AC and battery failure status. PG functions and virtual inputs are unavailable.

Frequently Asked Questions

What is the difference between a group object and a group address?

A group object is a gateway datapoint. A group address links that datapoint to other KNX devices or a visualisation; use the matching object size and datatype.

What should Module status report?

Module status (GO 1) reports 0 during normal operation. A non-zero value indicates an error.

How should I validate zone and area statuses?

Change an enabled zone or mapped area at the alarm panel and compare its state in ETS Group Monitor. Account for the zone offset, area mapping and Send area status setting.