Follow these steps in order. Keep the alarm panel configuration and the ETS project available during commissioning.
Prepare the installation
Interlogix ultraSync alarm system (NetworXConnect, xGen or ZeroWire), 12-30 VDC auxiliary supply, KNX bus and Ethernet connection. Have the matching ETS application and a valid alarm user code ready.
Connect and power the gateway
Connect KNX at the top and the 12-30 VDC auxiliary supply and Ethernet at the bottom. Check that the Network LED is on. For an NXG-8 with NXG-7002, follow the isolated LAN arrangement in Alarm system setup.
Configure the alarm and network
Create the alarm user “knx”; enable UltraSync and Status Broadcast. Open the gateway at 192.168.1.51, assign a suitable fixed IP and set Device IP to the alarm IP. Use the “knx” PIN in ETS. See Alarm system setup.
Configure the KNX device in ETS
Assign an unused physical address. Enter the valid user code and its length; enable only supported functions. Select zone count and offset, area count, area mapping and scene numbers. See ETS commissioning and ETS parameter reference.
Link group addresses and download
Assign a group address to each required object. Press the programming button to enter KNX programming mode and perform a full download for first commissioning. See ETS commissioning.
Validate status and control
In ETS Group Monitor, read Module status (0 for normal operation) and Firmware. Compare enabled zone and area statuses with the panel; check configured control commands and scenes. See Group addresses and validation.
Commissioning is complete when
The alarm-system connection operates, the firmware can be read on KNX and the configured status, control and scene objects respond as expected.