Skip to content
Elausys

KNX Gateways for Alarm Systems / AJAX-KNX User Manual

Configuring the alarm system

Set up SIA events and optional control permissions, and understand zone reporting and Night Mode.

elausys · 13 September 2026
On this page

Before configuring the gateway, prepare the Ajax system. First choose how the gateway receives the alarm events, then follow only the steps of that choice.

Choosing the Connection: Cloud or Local SIA

Both connections deliver the alarm events to the gateway. The choice is made on the Ajax configuration page of the gateway and can be changed at any time.

  • Cloud connection (default): a secured, encrypted cloud connection to Ajax. Internet access is required, and Elausys must be invited as Security Company. Every feature of the gateway is available.
  • Local SIA: the hub sends SIA reports to the gateway over the local network. No internet and no cloud are needed, but camera events, relay control and virtual inputs are not available, and areas cannot be armed or disarmed from KNX.
FeatureCloud connectionLocal SIA
Area status (armed, partial armed, disarmed, alarms)YesYes
Zone statusYesYes
AC and battery failureYesYes
Arm / partial arm / disarm from KNXYes—
Control of Ajax relays and sockets (PG)Yes—
Camera events: person, vehicle, pet… (PG)Yes—
Virtual inputs: panic alarm, photoYes—
Internet accessRequiredNot required
Elausys invited as Security CompanyRequiredNot required
SIA set-up on the hubNot requiredRequired
Zone numberingOrder of the devices in the Ajax appDevice number in the hub

Important: An Ajax hub sends its SIA reports to one destination only. With the cloud connection, the gateway leaves this SIA channel free: the hub can report by SIA to an external monitoring station while the gateway works through the cloud. The opposite is also possible: the gateway receives the local SIA reports while the monitoring station works through the Ajax cloud.

Note: The two connections do not number the zones the same way. Choose the connection before assigning the zone group objects in ETS.

Configure the Hub for SIA Events (local SIA)

With local SIA, the hub sends its events to the IP address of the gateway. Open the Space Settings, then Security Companies, then Monitoring Station and set:

  • Protocol: SIA DC-09 (SIA DCS).
  • IP Address of the Gateway and port 2410 (see Network Configuration under Configuring the gateway).
  • Object number : 3 letters of your choice (not relevant).
  • Encryption: off or on, if enabled use the SIA key shown on the Ajax configuration page of the gateway.

Note: A gateway updated from a firmware older than 1.0.2.0 keeps Encrypted SIA off, so that the hub keeps reporting. Switch it on in the Ajax configuration of the gateway, then enter its key on the hub.

Note: Skip this step with the cloud connection.

ajax-mbtcp-0220ed9ed331d1bb.png

Invite Elausys as Security Company (cloud connection)

With the cloud connection, invite Elausys as Security Company in the Ajax app: open the Space Settings, then Security Companies, and use Invite by email with the address info@elausys.be. This gives the gateway access to the hub, to receive its events and to send it commands.

ajax-mbtcp-499a07358a473c8f.png

Elausys accepts the invitation automatically, within a few minutes. The gateway then connects to the hub.

Note: Skip this step with local SIA.

Understanding Zone Reporting Behaviour

By default, AJAX motion detectors (MotionProtect) and door/window contacts (DoorProtect) only report zone status to the gateway when the system is armed or in night mode. This means that in the disarmed state, motion and door events are not transmitted to KNX.

If you want zone status available on KNX at all times — for example, motion-triggered lighting during the day or door-triggered welcome scenes — you can configure individual devices as Always Active (24hrs) in the AJAX app.

Important: Setting a device to Always Active means it will also trigger the alarm even when the system is not armed. This is by design in the AJAX platform. Use this setting selectively and only on zones where permanent reporting is genuinely needed.

Zone numbers: with the cloud connection, the zones follow the order of the detectors in the Ajax app (relays and sockets are left out). With local SIA, the zone number is the device number in the hub.

Understanding Night Mode (Partial Arming)

The Partial Arm function on the KNX gateway corresponds to the global Night Mode in the AJAX system. Therefore activating Partial Arm (ON) on any area will activate the Global Night Mode for the complete Hub.

Night Mode operates differently depending if groups are enabled or not in the Space Settings of the alarm panel.

When groups are enabled the night mode is independent from the arming or disarming of individual groups:

  • Disarming a group does not disable Night Mode. Night Mode remains active until explicitly disabled.
  • To disable Night Mode, you must send the Partial Arm (OFF) command using the corresponding group object.

When groups are disabled (1 area only), Night Mode ends when area 1 is armed or disarmed, and Partial Arm (OFF) disarms the hub.

Frequently Asked Questions

Should I use the cloud connection or local SIA?

The cloud connection (default) gives every feature, including arming from KNX, PG and virtual inputs, and needs internet access and Elausys invited as Security Company. Local SIA works without internet but only reports statuses.

Which SIA destination should I configure?

With local SIA only: set protocol SIA DC-09, the gateway IP address and port 2410 in Space Settings, Security Companies, Monitoring Station, and an Object number of three letters. If encryption is on, enter the SIA key shown on the Ajax configuration page of the gateway.

When can control commands start working?

With the cloud connection, invite info@elausys.be as Security Company using Invite by email. Elausys accepts it automatically within a few minutes, then the gateway connects to the hub.

Why are there no detector events when the alarm is disarmed?

Motion and door detectors normally report when armed or in Night Mode. Always Active (24hrs) enables permanent reporting, but also allows those detectors to trigger the alarm while disarmed.

Keep exploring

Find the other guides for this product in the documentation.

Back to AJAX-KNX User Manual