Connected LED off (cloud connection)
Check, in this order: internet access of the gateway (no port forwarding is needed; on a network that filters outgoing traffic, allow TCP 7443 and DNS); the Hub ID; that Elausys was invited as Security Company. The Ajax configuration page shows the state of the Cloud API.
No command from KNX
Arming, PG and virtual inputs need the cloud connection: check that the Cloud connection switch is on and that the Cloud API shows Connected.
Web page does not open
Use https:// followed by the IP address of the gateway and accept the certificate of the gateway. A forgotten password is removed by a factory reset.
Zone numbers changed
The connection was switched between cloud and local SIA: the two do not number the zones the same way. Check the zone group objects.
Not understanding zone reporting behaviour
AJAX sensors only report zone status to KNX when the system is armed or in night mode. Setting devices to Always Active enables daytime reporting, but also means those zones will trigger the alarm when the system is disarmed. Plan which zones genuinely need 24/7 KNX reporting.
Not inviting Elausys as Security Company
With the cloud connection, the gateway does not reach the hub until Elausys is invited as Security Company in the AJAX app. Internet access is also required.
Skipping the scene assignment
The gateway supports automatic scene recall, but scenes default to 0 (disabled). You must configure them manually in ETS for every area status you want to automate.
Incorrect area count with AJAX groups
When groups are enabled in AJAX, at least two areas must be configured in ETS to switch from global to individual group commands. Configuring only one area when groups are active will result in incorrect behaviour.
Expecting disarm to exit Night Mode
Disarming a group does not disable Night Mode when groups are enabled. You must explicitly send a Partial Arm (OFF) command to disable Night Mode. Design your KNX logic to handle this independently.
Ethernet connection loss
If the Ethernet connection drops, the Network and Connected LEDs turn off. The Module Status group object (GO 1) will send an error code to KNX, allowing your visualisation to display a connectivity fault. Zone statuses will hold their last known state until communication is restored.
Factory Default Reset
To restore the factory defaults, toggle KNX programming mode four times in succession within 30 seconds using the KNX programming button on the front of the gateway. The Network LED blinks 4 times and the gateway restarts with its default settings: IP address 192.168.1.51, no Hub ID, no web password. The ETS application, the cloud registration of the gateway and its HTTPS certificate are kept: the ETS application does not need to be downloaded again.
KNX status and programming mode
The KNX card of the Network settings page displays the KNX bus status and allows you to switch KNX programming mode on or off.