ETS parameter reference

The complete ETS parameter reference, supported functions and area scene settings.

elausys · 15 September 2026
On this page

General settings

Set these options in the General section of the device Parameters tab. The availability limits for this product take precedence over the generic ETS options.

ParameterValuesConfiguration guidance
Use PG ControlNot used (default) / UsedWhen this parameter is set to “Used”, the PG control group objects are made available.
Use PG StatusNot used (default) / UsedWhen this parameter is set to “Used”, the PG status group objects are made available.
Number of PG16 (default) / 32Number of PG control and status group objects to be used
Use Zone StatusNot used / Used (default)When this parameter is set to “Used”, the zone status group objects are made available.
Number of zones16 (default) / 32 / 48 / 64 / 72 / 96Number of zone status group objects to be used.
Zones offset0 (default) / 96An offset of 0 will use zones 1 to 96 from the alarm system whereas an offset of 96 will use zones 97 to 192
Use Virtual inputsNot used (default) / UsedThis parameter must be set to “Not used” for the Jablotron interface. Virtual inputs are not available on this device.
Number of areas1 (default) / 2 / 3 / 4Number of areas to control/monitor from the KNX interface
Send area statusON / OFF / ON/OFF (default)Area status object can be configured to send only the changes to ON values, only the changes to OFF values or both ON and OFF values
User codeText field (format 1*1234)When using control commands from KNX, a valid user code of up to 6 digits is required. This applies to area control (arm, disarm,…)
User code length4..6Number of digits for the user code
Use Power supply statusNot used (default) / UsedThis parameter must be set to “Not used” for the Jablotron interface. Power supply status is not available on this device.
PG and Zone startup behaviorSwitch OFF (default) / Switch ON / MemoryInternal status of group object after restart. Memory will restore the state of group objects before power loss.
Device OptionsText stringDevice options are not available on this device.

Functional settings

PG control and status

PG Control and PG Status must be enabled in the general parameters to enable the corresponding group objects. Depending on the general parameter “Number of PG”, 16 or 32 PGs are listed in the group objects.

The status of each PG from the Jablotron alarm system can be monitored by a Group object. The PG can be configured in the Jablotron system to send status based on specific events. Each PG of the Jablotron alarm system can also be controlled from KNX by a Group object.

Zone status

Depending on the general parameter “Number of zones”, up to 96 zones are listed in the group objects.

The status of each zone from the Jablotron alarm system can be monitored by a Group object.

The general parameter “Zones offset” allows the use of zones 1 to 96 from the alarm system or zones 97 to 192.

Area settings and scenes

Depending on the general parameter “Number of areas”, up to 4 areas are listed in the group objects.

Each area can be controlled by using the 3 group objects: Arm, partial arm or disarm. Several statuses are available and have a dedicated group object.

CONTROL OBJECTVALUE ONVALUE OFF
Arm (switch)ArmDisarm
Partial arm (switch)Partial ArmDisarm
Disarm (trigger)DisarmDisarm

For each area, a tab is made visible to configure the area parameters.

Areas are configured for areas 1 to 4 of the alarm system but by changing the parameter “Area mapping” it is also possible to cover the areas 5 to 8.

A scene can be assigned to each status. This scene number will be recalled each time the area status is active (ON).

Leave the scene number to 0 to disable the scene control.

STATESCENE
Disarmed0..64
Entry0..64
Exit0..64
Armed0..64
Partial armed0..64
Fire alarm0..64
Siren ON (Audible alarm)0..64
Panic alarm (Silent alarm)0..64
Intrusion alarm0..64

Frequently Asked Questions

How does the zone offset work?

Offset 0 selects alarm zones 1 to 96. Offset 96 selects zones 97 to 192. The Number of zones parameter determines how many status objects are available.

How do I disable a scene recall?

Leave its scene number at 0. Scene numbers 1 to 64 recall the selected KNX scene when the corresponding area status becomes active.

Are all generic ETS options supported?

Virtual inputs, power supply status and Device Options are unavailable. The alarm service mode disables the RS485 and KNX interface.