Link each required object
A group object (GO) is a datapoint in the gateway. A group address (GA) links it to other KNX devices or a visualisation. Match each group address to the size and datatype in Communication object reference.
| Check | Expected result |
|---|---|
| Module status (GO 1) | 0 when operating normally; a non-zero code indicates an error. |
| Firmware (GO 2) | A version string is returned. Check the firmware applicability in Firmware and technical data. |
| Zone status | Open and close an enabled zone and compare the KNX value with the alarm system. Account for the configured zone offset. |
| Area status | Confirm that status changes follow the mapped area and the Send area status setting. |
| Area control | Check arm, partial arm and disarm for the mapped area using the configured user code. See the ON/OFF behaviour in ETS parameter reference. |
| Scenes (GO 233) | An active area status sends the configured scene number. Scene 0 disables the recall. |
Check enabled PG controls and PG status against the panel. Virtual inputs and power supply status are unavailable. The RX/TX LED flashes for RS485 telegrams.