KNX Gateways for Inverters / INV-KNX Fronius User Manual

ETS commissioning

Physical addressing, application settings, group-address links and ETS downloads for INV-KNX Fronius.

elausys · 13 September 2026
On this page

Assign the physical address

Add the appropriate Elausys INV-KNX application to the ETS project. Choose an unused physical address in the project topology; Press the gateway P button to enter programming mode and download the physical address.

Set the application parameters

Once a KNX physical address is set, open the parameter tab to configure the interface.

Select the type of AC network (single phase or tri-phase).

Set the inverter model to 3 for Fronius inverters or 6 for Fronius Symo Hybrid inverters.

Choose the refresh rate (min) for the complete set of data.

Select if battery 1 is available on the inverter.

Select Powermeter if a Fronius Smart Meter is available.

Fronius Smart meter modbus ID must be set in the “Device Options” field.

Smartmeter ID must be checked in the inverter configuration (default is 200 or 240).

Set the timezone and daylight-saving option when using weekly calendar logic. See Section 6 for the full parameter values and limitations.

A group address (GA) must be assigned to each group object (GO) needed by the application.

Open the Group Objects tab of the device and assign a GA to the objects as needed.

When GO and parameters are all configured, download the KNX Interface application to the device. The first download requires to press the programming button on the device to set the device in KNX programming mode then perform a full download.

Verify the result

Use ETS Group Monitor to check module status, read the firmware version and compare live measurements with the inverter. Follow Section 7 before enabling automation.

ETS software

The gateway is configured with ETS from the KNX Association. ETS Demo supports projects of up to five KNX modules; the gateway occupies one module.

Manual navigation

All chapters of the INV-KNX Fronius user manual

Frequently Asked Questions

What is required for the first ETS download?

Assign the physical address using the P button for programming mode. Configure the application parameters and required group-address links, then perform a full download.

What should I check after downloading the application?

Use ETS Group Monitor to read module status and firmware, then compare live measurements with the inverter after the polling interval.