Group addresses and data validation

Commissioning checks and interpretation of the KNX measurements supplied by INV-KNX Fronius.

elausys · 15 September 2026
On this page

A group object (GO) is a device datapoint. A group address (GA) links it to other KNX devices or a visualisation. Assign group addresses only to the objects needed by the project and match their datatypes to Section 8.

Commissioning checks

GOObjectWhat to check
1Module status0 means normal operation; investigate a non-zero status.
2Firmware versionRead the version and check the applicability in Section 11.
24AC PowerCompare the value with the inverter display or application.
30AC EnergyCompare the accumulated value and units.
42 / 43Battery power / SOCWhere supported, enable Battery 1 and compare with the battery state.
55PowermeterWhere supported, enable the meter and verify the measurement direction.

Check power directions and availability

GO 40 Daily Energy Yield: (NOT USED)

GO 41 Battery 1 Running Status: 0: OFF 1: EMPTY 6: DISCHARGING 7: CHARGING 9: FULL 10: HOLDING 11: TESTING

GO 42 Battery 1 power: (NOT USED)

GO 49 Battery 2 power: (NOT USED)

GO 55 Powermeter: Fronius Smart meter (meter modbus ID must be set in the ETS parameter Options)

Unavailable objects

Objects marked NOT USED are unavailable for this application even when the generic ETS interface exposes them. Check equipment and operating conditions before treating zero values as a fault.

Manual navigation

All chapters of the INV-KNX Fronius user manual

Frequently Asked Questions

What is the difference between a group object and a group address?

A group object is a device datapoint. A group address links that datapoint to other KNX devices or a visualisation. Assign addresses to the required objects and use the matching datatypes.

Does a zero measurement always indicate a fault?

No. Check the operating conditions and equipment availability before treating zero as a communication fault. Also wait for the configured polling interval.

Is Fronius Battery 1 power available?

GO 42 Battery 1 power is marked NOT USED for this application. Enabling the generic object does not make this measurement available.